ENVISION 7-25 TONS INSTALLATION MANUAL

35

Object Type

Type Enumeration

Instance

Name

Enumeration

Analog Value

2

1

Present_Value

85

WFI##########.Occupied Cool.Present_Value

Occupied Cooling Setpoint Input (Read/Write)
Standby Cooling Setpoint Input (Read/Write)

Analog Value

2

3

Present_Value

85

WFI##########.Unoccupied Cool.Present_Value

Unoccupied Cooling Setpoint Input (Read/Write)

Analog Value

2

2

Present_Value

85

WFI##########.Occupied Heat.Present_Value

Occupied Heating Setpoint Input (Read/Write)
Standby Heating Setpoint Input (Read/Write)

Analog Value

2

4

Present_Value

85

WFI##########.Unoccupied Heat.Present_Value

Unoccupied Heating Setpoint Input (Read/Write)

Analog Value

2

7

Present_Value

85

WFI##########.Min Clg Setpt.Present_Value

Minimum Cooling Setpoint Input (Read/Write)

Analog Value

2

6

Present_Value

85

WFI##########.Max Htg Setpt.Present_Value

Maximum Heating Setpoint Input (Read/Write)

Analog Input

0

1

Present_Value

85

WFI##########.Space Temp.Present_Value

Space or Zone Temperature Value (Read Only)

Analog Input

0

2

Present_Value

85

WFI##########.Discharge Air Temp.Present_Value

Discharge Air Temp Field Supplied Only (Read Only)

Analog Input

0

5

Present_Value

85

WFI##########.Effective Clg Setpt.Present_Value

Effective Cooling Setpoint Value (Read Only)

Analog Input

0

6

Present_Value

85

WFI##########.Effective Htg Setpt.Present_Value

Effective Heating Setpoint Value (Read Only)

Analog Output

1

2

Present_Value

85

WFI##########.Space temp Ovrd.Present_Value

Space or Zone Temperature Value Override(Write)
Heating Freeze Protection Temperature Setpoint Value (Read/Write)
Heating Freeze Protection Temperature Setpoint Value (Read/Write)
1st Stage Compressor Heating Output (Read Only)
1st Stage Compressor Cooling Output (Read Only)
Fan Output (Read Only)

Multistate Input

13

2

Present_Value

85

WFI##########.Mode.Present_Value

Unit Mode of Operation (Read Only)
Unit Alarm mode (Read Only)
Heating/Cooling Prop Band Input (Read/Write)

Analog Value

2

9

Present_Value

85

WFI##########.Remote Setpt Min.Present_Value

Warm/Cool Adjust Min (Read/Write)

Analog Value

2

8

Present_Value

85

WFI##########.Remote Setpt Max.Present_Value

Warm/Cool Adjust Max (Read/Write)

Analog Value

2

10

Present_Value

85

WFI##########.Zone Temp Offset.Present_Value

Space or Zone Temperature Sensor Calibration Input (Read/Write)

Analog Output

1

1

Present_Value

85

WFI##########.Common Setpoint.Present_Value

General Setpoint Input (Read/Write)

Analog Input

0

3

Present_Value

85

WFI##########.Freez Temp 1.Present_Value

Heating Freeze Protection Temperature 1 Value (Read Only)

Analog Input

0

3

Present_Value

85

WFI##########.Freez Temp 2.Present_Value

Heating Freeze Protection Temperature 2 Value (Read Only)

Analog Input

0

8

Present_Value

85

WFI##########.nvoAlarms.Present_Value

Alarms Enumerated [0=no alarms, 1=condensate alarm, 2=Compressor Hi Discharge Pressure
alarm, 3=Compressor low Suction Pressure alarm, 4=Freeze protection alarm, 8=Faulty Freeze
Sensor alarm, 9=Loss of Charge] (Read Only)

Analog Input

0

9

Present_Value

85

WFI##########.Economizer Temp.Present_Value

Main Loop Temp for Economizer Control (Read Only)

Analog Input

2

5

Present_Value

85

WFI##########.Economizer Setpt.Present_Value

Setpoint for Economizer (Read/Write)

Analog Value

2

11

Present_Value

85

WFI##########.EconomizerTempOffset.Present_Value

Economizer Temperature Sensor Calibration Input (Read/Write)

Analog Input

0

7

Present_Value

85

WFI##########.Freez Temp Limit.Present_Value

Heating Freeze Protection Temperature Setpoint Value (Read Only)
Compressor Stage Lead/Lag hour setting (Read/Write)

Multistate Input

13

1

Present_Value

85

WFI##########.Effective Occupancy.Present_Value

Effective Occupancy State (Read Only)

Multistate Output

14

1

Present_Value

85

WFI##########.Occupancy Command.Present_Value

Occupancy Override Command Input (Read/Write)

Multistate Output

14

6

Present_Value

85

WFI##########.Emergency Override.Present_Value

Emergency Override Input (Read/Write)

Binary Input

3

1

Present_Value

85

WFI##########.Fan Cmd Status.Present_Value

Fan Output Status (Read Only)
Accessory 2 Output Status (Read Only)
Accessory 1 Output Status (Read Only)
Alarm Output Status (Read Only)

Multistate Output

14

7

Present_Value

85

WFI##########.Alarm Reset.Present_Value

Alarm Reset Input (Read/Write)

Multistate Output

14

2

Present_Value

85

WFI##########.Fan Command (G).Present_Value

Network equivelant of a thermostatic 'G' call. (Write)

Multistate Output

14

3

Present_Value

85

WFI##########.Comp1 Command (Y1).Present_Value

Network equivelant of a thermostatic 'Y1' call. (Write)

Multistate Output

14

4

Present_Value

85

WFI##########.Comp2 Command (Y2).Present_Value

Network equivelant of a thermostatic 'Y2' call. (Write)

Multistate Output

14

5

Present_Value

85

WFI##########.Rev Vlv Cmd (O).Present_Value

Network equivelant of a thermostatic 'O' call. (Write)

Binary Input

3

2

Present_Value

85

WFI##########.Comp1 Cmd Status.Present_Value

Compressor 1 Command Status (Read Only)

Binary Input

3

4

Present_Value

85

WFI##########.Reversing Valve.Present_Value

Reversing Valve Output Status (Read Only)
Occupancy Supervisory Scheduler Command Input (Read/Write)

Binary Input

3

3

Present_Value

85

WFI##########.Comp2 Cmd Status.Present_Value

Compressor 2 Command Status (Read Only)
Compressor Stage Lead/Lag Enable/Disable (Read/Write)

Multistate Value

19

1

Present_Value

85

WFI##########.Economizer Ena/Dis.Present_Value

Water Side Economizer Enable/Disable (Read/Write)

Multistate Input

13

3

Present_Value

85

WFI##########.Compressor/Fan Prove.Present_Value

Compressor/Fan Proving Switch Status (Read Only)

Multistate Output

14

8

Present_Value

85

WFI##########.Emergency Heat BO5.Present_Value

Command for output BO5 used for Emg Heat-Interlocked with Fan DP9Read/Write)

Binary Input

3

5

Present_Value

85

WFI##########.BO5 ElecHeat.Present_Value

Value Output for BO5 used for Emg Heat (Read Only)

Multistate Output

14

9

Present_Value

85

WFI##########.BO9.Present_Value

Command for output BO9(Read/Write)

Binary Input

3

9

Present_Value

85

WFI##########.BO9 Output.Present_Value

Value output for BO9 (Read Only)

Point Description

Object Identifier

Property

BACnet

Full Reference

Optional FX10 Microprocessor Control - BACnet