ENVISION 7-25 TONS INSTALLATION MANUAL

40

Operating Parameters

Pressure Drop

30°F

50°F

70°F

90°F

110°F

10.0

2.48

2.36

2.29

2.21

2.14

080

16.0

5.96

5.62

5.22

4.89

4.69

22.0

10.91

10.38

9.73

9.12

8.50

12.0

2.22

2.00

1.92

1.83

1.67

095

18.0

4.62

4.02

3.80

3.75

3.65

24.0

7.31

6.81

5.80

5.60

5.19

16.0

2.03

1.93

1.88

1.80

1.50

120

22.0

3.69

3.58

3.40

3.19

2.99

28.0

5.58

5.50

5.32

5.00

4.84

20.0

1.20

1.19

1.18

1.17

1.16

160

28.0

2.64

2.50

2.37

2.24

2.12

35.0

3.72

3.65

3.41

3.36

3.21

22.0

1.50

1.50

1.50

1.50

1.50

180

34.0

3.95

3.90

3.85

3.80

3.75

45.0

6.40

6.10

6.00

5.80

5.70

30.0

0.90

0.82

0.75

0.69

0.63

240

45.0

2.22

2.06

1.91

1.77

1.64

60.0

3.47

3.29

3.06

2.88

2.40

35.0

1.84

1.60

1.39

1.21

1.05

300

56.0

4.09

3.88

3.69

3.51

3.33

75.0

6.10

5.95

5.77

5.45

5.10

Model

GPM

Pressure Drop (psi)

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

080-300

Superheat

080-300

Subcooling

Water Temp

Rise °F

Air Temp

Drop °F DB

1.5

110-130

160-190

10-17

13-17

17-22

20-30

3.0

110-130

160-190

20-30

11-15

8-12

20-30

1.5

120-140

260-300

9-13

15-19

17-22

20-30

3.0

120-140

260-300

9-13

11-15

8-12

20-30

1.5

130-150

340-380

8-12

15-19

15-19

15-25

3.0

130-150

340-380

8-12

11-15

7-11

15-25

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

080-300

Superheat

080-300

Subcooling

Water Temp

Drop °F

Air Temp

Rise °F DB

1.5

-

-

-

-

-

-

3.0

60-80

280-310

10-14

5-12

4-8

20-30

1.5

80-110

300-330

8-12

5-12

6-12

20-30

3.0

80-110

300-330

8-12

5-12

6-12

20-30

1.5

110-140

330-360

8-12

1-8

10-15

30-40

3.0

110-140

330-360

8-12

1-8

10-15

30-40

7/25/07

70

50

30

Heating

70

90

Water Flow

GPM/Ton

Entering

Water Temp

°F

Cooling

Entering

Water Temp

°F

Water Flow

GPM/Ton

50

Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.

Heating performance based on entering air temperature of 70º F DB.