ENVISION 7-25 TONS INSTALLATION MANUAL

22

Airflow in CFM with dry coil and clean air filter.

External Static Pressure (in. w.g.)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.2

1.4

1.6

1.8

2.0

MTR/SHEAVE

2.0

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

BHP

1.46

1.49

1.77

1.94

2.11

2.29

2.32

2.39

2.65

2.72

2.80

2.36

RPM

677

696

745

778

810

841

858

878

912

932

951

994

TURNS OPEN

5.0

4.0

3.0

2.0

1.0

4.0

3.5

3.0

2.0

1.5

1.0

4.5

MTR/SHEAVE

2.0

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

BHP

1.55

1.70

1.86

2.03

2.21

2.39

2.42

2.50

2.75

2.83

2.91

2.63

2.61

RPM

674

708

742

774

806

837

853

873

907

926

945

981

1010

TURNS OPEN

5.0

4.0

3.0

2.0

1.0

4.0

3.5

3.0

2.0

1.5

1.0

4.5

4.0

MTR/SHEAVE

2.0

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

BHP

1.63

1.79

1.96

2.13

2.31

2.49

2.52

2.60

2.85

2.93

3.01

2.87

2.87

2.86

RPM

671

705

738

771

802

833

849

869

903

922

940

969

997

1025

TURNS OPEN

5.0

4.0

3.0

2.0

1.0

4.0

3.5

3.0

2.0

1.5

1.0

4.5

4.0

3.5

MTR/SHEAVE

2.0

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

BHP

1.72

1.88

2.04

2.22

2.40

2.58

2.62

2.70

2.95

3.03

3.11

3.09

3.10

3.11

RPM

668

702

735

767

799

829

845

864

898

917

935

959

985

1012

TURNS OPEN

5.0

4.0

3.0

2.0

1.0

4.0

3.5

3.0

2.0

1.5

1.0

4.5

4.0

3.5

MTR/SHEAVE

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

BHP

1.96

2.13

2.31

2.49

2.68

2.71

2.79

3.05

3.13

3.21

3.29

3.31

3.33

RPM

699

732

764

795

825

841

860

894

912

931

949

975

1001

TURNS OPEN

4.0

3.0

2.0

1.0

4.0

3.5

3.0

2.0

1.5

1.0

4.5

4.0

3.5

MTR/SHEAVE

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

BHP

2.21

2.39

2.58

2.77

2.81

2.89

3.13

3.22

3.31

3.39

3.51

3.54

3.56

RPM

729

761

792

821

837

856

890

908

926

944

965

990

1016

TURNS OPEN

3.0

2.0

1.0

4.0

3.5

3.0

2.0

1.5

1.0

4.5

4.0

3.5

3.0

MTR/SHEAVE

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

BHP

2.48

2.66

2.85

2.90

2.98

3.23

3.32

3.40

3.48

3.61

3.73

3.76

RPM

758

788

818

833

852

885

904

922

939

960

980

1005

TURNS OPEN

2.0

1.0

4.0

3.5

3.0

2.0

1.5

1.0

4.5

4.0

3.5

3.0

A=Std Static/Std Mtr;B=Low Static/Std. Mtr;C=High Static/Std. Mtr;D=Std Static/Large Mtr;E=High Static/Large Mtr
Units factory shipped with standard static sheave and drive at 3.0 turns open (9500 cfm @ 0.7 in. ESP). Other speeds require field selection.

ISO/AHRI rating point with standard static sheave and drive at 3.0 turns open (9500 cfm @ 0.7 in. ESP). Other speeds require field selection.

For applications requiring higher static pressures, contact your local representative.

Performance data does not include drive losses and is based on sea level conditions.

Do not operate in gray region. "na" = information not available at time of printing.

All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.

For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).

Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, and 400 fpm by 0.12 in. wg.

BHP is given for each blower. Multiply BHP x 2 for unit BHP.

7/25/07

9600

10000

10400

10800

Rated CFM

8400

8800

9200

A

B

C

NLV300 - Blower Performance Data

Belt Drive