Ac e d, Nlv095 - blower performance data – WaterFurnace Envision (XL) User Manual

Page 16

Advertising
background image

ENVISION 7-25 TONS INSTALLATION MANUAL

17

Airflow in CFM with dry coil and clean air filter.

External Static Pressure (in. w.g.)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.2

1.4

1.6

1.8

2.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

4.0

4.0

BHP

0.61

0.64

0.66

0.68

0.76

0.81

0.87

0.89

0.94

1.05

RPM

581

601

621

663

703

739

774

784

827

867

TURNS OPEN

5.0

4.5

4.0

3.0

2.0

1.5

1.0

0.0

2.0

1.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

4.0

4.0

4.0

BHP

0.65

0.66

0.68

0.75

0.86

0.87

0.88

1.02

1.05

1.14

1.23

RPM

580

600

621

662

701

722

742

782

805

855

905

TURNS OPEN

5.0

4.5

4.0

3.0

2.0

1.5

1.0

0.0

2.5

1.5

0.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

BHP

0.72

0.73

0.74

0.84

0.96

0.98

0.99

1.13

1.14

1.17

1.23

1.36

1.48

1.59

1.69

RPM

579

600

620

660

700

721

741

780

797

813

845

890

940

960

991

TURNS OPEN

5.0

4.5

4.0

3.0

2.0

1.5

1.0

0.0

3.0

2.5

2.0

1.0

0.0

3.0

2.5

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

5.0

BHP

0.79

0.80

0.82

0.93

1.06

1.08

1.10

1.25

1.26

1.31

1.36

1.49

1.62

1.67

1.85

2.03

RPM

578

599

619

659

699

719

739

778

795

819

843

890

937

942

967

991

TURNS OPEN

5.0

4.5

4.0

3.0

2.0

1.5

1.0

0.0

3.0

2.5

2.0

1.0

0.0

3.0

2.5

2.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

5.0

5.0

BHP

0.84

0.89

1.01

1.15

1.17

1.20

1.35

1.36

1.42

1.48

1.52

1.61

1.82

1.90

1.99

2.03

RPM

597

619

658

697

718

738

776

794

818

841

857

888

940

963

986

1034

TURNS OPEN

4.5

4.0

3.0

2.0

1.5

1.0

0.0

3.0

2.5

2.0

1.5

1.0

3.0

2.5

2.0

1.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

5.0

5.0

5.0

BHP

0.97

1.09

1.23

1.26

1.29

1.45

1.47

1.53

1.60

1.67

1.74

1.95

2.05

2.14

2.19

2.41

RPM

618

657

696

716

736

775

792

815

838

862

885

937

960

983

1031

1077

TURNS OPEN

4.0

3.0

2.0

1.5

1.0

0.0

3.0

2.5

2.0

1.5

1.0

3.0

2.5

2.0

1.0

0.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

5.0

5.0

5.0

BHP

1.17

1.32

1.35

1.38

1.55

1.57

1.64

1.71

1.78

1.86

2.09

2.18

2.28

2.34

2.57

RPM

656

695

715

735

773

790

814

837

860

883

935

958

981

1029

1074

TURNS OPEN

3.0

2.0

1.5

1.0

0.0

3.0

2.5

2.0

1.5

1.0

3.0

2.5

2.0

1.0

0.0

Bold Face Requires Larger 2 HP Motor

7/25/07

A=Std Static/Std Mtr;B=Low Static/Std. Mtr;C=High Static/Std. Mtr;D=Std Static/Large Mtr;E=High Static/Large Mtr
Units factory shipped with standard static sheave and drive at 2 turns open (2800 cfm @ 0.6 in. ESP). Other speeds require field selection.

ISO/AHRI rating point with standard static sheave and drive at 1 turns open (2800 cfm @ 0.7 in. ESP). Other speeds require field selection.

For applications requiring higher static pressures, contact your local representative.

Performance data does not include drive losses and is based on sea level conditions.

Do not operate in gray region. "na" = information not available at time of printing.

All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.

For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).

Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, and 400 fpm by 0.12in. wg.

3200

3400

3600

3800

Rated CFM

2600

2800

3000

A

C

E

D

NLV095 - Blower Performance Data

Belt Drive

Advertising