ENVISION 7-25 TONS INSTALLATION MANUAL

24

Airflow in CFM with dry coil and clean air filter.

Rated CFM

External Static Pressure (in. w.g.)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.2

1.4

1.6

1.8

2.0

MTR/SHEAVE

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

4.0

4.0

4.0

4.0

5.0

2600

BHP

0.44

0.47

0.52

0.57

0.66

0.78

0.79

0.80

0.92

0.97

1.08

1.18

1.37

1.56

RPM

584

625

667

708

757

806

831

856

905

960

1021

1082

1142

1202

TURNS OPEN

5.0

4.0

3.0

2.0

4.0

3.0

2.5

2.0

1.0

3.0

2.0

1.0

0.0

3.0

MTR/SHEAVE

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

4.0

4.0

4.0

4.0

5.0

5.0

2800

BHP

0.51

0.56

0.61

0.67

0.77

0.89

0.90

0.91

1.06

1.11

1.14

1.38

1.44

1.59

1.73

RPM

583

625

665

707

756

804

829

854

902

933

982

1055

1100

1156

1212

TURNS OPEN

5.0

4.0

3.0

2.0

4.0

3.0

2.5

2.0

1.0

3.5

2.5

1.5

0.5

3.5

2.5

MTR/SHEAVE

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

4.0

4.0

4.0

4.0

4.0

5.0

5.0

3000

BHP

0.57

0.64

0.70

0.76

0.87

1.00

1.01

1.03

1.19

1.25

1.28

1.33

1.59

1.64

1.68

1.91

RPM

582

624

665

705

754

802

827

852

900

930

955

1005

1078

1110

1169

1228

TURNS OPEN

5.0

4.0

3.0

2.0

4.0

3.0

2.5

2.0

1.0

3.5

3.0

2.0

0.5

0.0

3.0

2.0

MTR/SHEAVE

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

3200

BHP

0.70

0.78

0.86

0.97

1.11

1.13

1.15

1.31

1.31

1.38

1.44

1.61

1.69

1.80

2.02

RPM

623

664

704

753

801

826

851

899

919

949

978

1036

1086

1137

1196

TURNS OPEN

4.0

3.0

2.0

4.0

3.0

2.5

2.0

1.0

4.0

3.5

3.0

2.5

1.5

3.5

2.5

MTR/SHEAVE

2.0

2.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

3400

BHP

0.85

0.94

1.07

1.21

1.24

1.26

1.42

1.43

1.50

1.57

1.65

1.71

1.76

2.10

2.35

RPM

663

703

752

800

825

849

896

917

947

976

1020

1057

1094

1164

1223

TURNS OPEN

3.0

2.0

4.0

3.0

2.5

2.0

1.0

4.0

3.5

3.0

2.5

1.8

1.0

3.0

2.0

MTR/SHEAVE

2.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

3600

BHP

1.01

1.16

1.31

1.34

1.37

1.54

1.55

1.63

1.70

1.78

1.87

2.06

2.15

2.40

RPM

702

751

798

823

848

894

915

945

974

1003

1031

1088

1133

1191

TURNS OPEN

2.0

4.0

3.0

2.5

2.0

1.0

4.0

3.5

3.0

2.5

2.0

1.5

3.5

2.5

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

3800

BHP

1.23

1.40

1.44

1.48

1.66

1.67

1.75

1.83

1.91

2.00

2.10

2.19

2.44

RPM

750

797

821

845

893

913

942

971

1000

1029

1086

1102

1160

TURNS OPEN

4.0

3.0

2.5

2.0

1.0

4.0

3.5

3.0

2.5

2.0

1.5

4.0

3.0

Bold Face Requires Larger 2 HP Motor

A=Std Static/Std Mtr;B=Low Static/Std. Mtr;C=High Static/Std. Mtr;D=Std Static/Large Mtr;E=High Static/Large Mtr
Units factory shipped with standard static sheave and drive at 2 turns open (3200 cfm @ 0.6 in. ESP). Other speeds require field selection.

ISO/AHRI rating point with standard static sheave and drive at 2 turns open (3200 cfm @ 0.6 in. ESP). Other speeds require field selection.

For applications requiring higher static pressures, contact your local representative.

Performance data does not include drive losses and is based on sea level conditions.

Do not operate in gray region. "na" = information not available at time of printing.

All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.

For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).

Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, and 400 fpm by 0.12in. wg.