Optional fx10 microprocessor control cont – WaterFurnace Envision (XL) User Manual

Page 28

Advertising
background image

ENVISION 7-25 TONS INSTALLATION MANUAL

29

operation until the controller is reset. If the control faults

due to the low pressure input (BI-3) being open during

the pre-compressor startup check, the control will go into

lockout mode immediately, disabling the compressor from

starting and enabling the alarm output (BO-6). The lockout

condition can be reset by powering down the controller, by

a command from the BAS, or by the holding the ESC and

Return keys on the MUI for 5 seconds.

Freeze Detection (AI-5)

The freeze detection sensor will monitor the liquid

refrigerant temperature entering the water coil in the

heating mode. If the temperature drops below the freeze

detection trip point for the recognition delay period,

the condition will be recognized as a fault. The freeze

detectopm trip point will be factory set for 30°F and will

be field selectable for 15°F by removing a jumper wire on

BI-5. The freeze detection fault condition will be bypassed

2 minutes at normal compressor startup, to allow the

refrigeration circuit to stabilize. If the freeze detection

sensor becomes unreliable at any time compressor

operation will immediately be suspended until the problem

is corrected. This should be displayed as an alarm on the

BAS and the MUI. This alarm will be reported a “Water Low

Temp Limit” fault.

High Pressure (BI-11)

The high-pressure switch shall be a normally closed (NC)

switch that monitors the systems refrigerant pressure. If

the input senses the high-pressure switch is open it must

disable the compressor output immediately and count the

fault. The compressor minimum on time does not apply if

the high-pressure switch opens. The compressor will not

restart until the compressor short cycle time delay has

been satisfied.

Low Pressure (BI-3)

The low-pressure switch shall be a normally closed (NC)

switch that monitors the systems refrigerant pressure.

The input shall be checked 15 seconds before compressor

start up to be sure the pressure switch is closed and then

ignored for the first 2 minutes after the compressor output

(BO-2) is enabled. If the switch is open continuously for

(30) seconds during compressor operation the compressor

output (BO-2) will be disabled. The compressor will not

restart until the compressor short cycle time delay has

been satisfied.

Alarm Output (BO-6)

The alarm output will be enabled when the control is in

the lockout mode and will be disabled when the lockout is

reset.

Test Mode

Raising the zone temperature input (AI-1) reading to 180

– 220 degrees F or by holding the ESC and down arrow

keys on the MUI for 5 seconds will put the control into

test mode. In test mode the random start delay and the

compressor fixed on delay time will both be shortened

to 5 seconds and the reversing valve will be allowed to

cycle with out shutting down the compressor. If an MUI is

connected to the control LED 8 will flash and the words

“Test Mode Enabled” will be shown on the LCD display

when the control is in test mode. Test mode will be disabled

after a power cycle, 30 minute timeout, or by holding the

ESC and Up arrow keys on the MUI.

Power Fail Restart

When the controller is first powered up, the outputs will be

disabled for a random start delay. The delay is provided

to prevent simultaneous starting of multiple heat pumps.

Once the timer expires, the controller will operate normally.

Random Start Delay

This delay will be used after every power failure, as well as

the first time the compressor is started after the control

exits the unoccupied mode or the emergency shutdown

mode. The delay should not be less than 1 second and not

longer than 120 seconds. If the control is in test mode the

random start delay will be shortened to 5 seconds.

Compressor Fixed On Delay Time

The Compressor Fixed On Delay Time will ensure that the

compressor output (B02) is not enabled for (90) seconds

after the control receives a call to start the compressor.

This delay is adjustable from 30 – 300 seconds over a BAS

or a MUI. If the control is in test mode the Compressor

Fixed On Delay Timer will be shortened to 5 seconds.

Compressor Minimum On Delay

The compressor minimum on delay will ensure that the

compressor output is enabled for a minimum of (2)

minute each time the compressor output is enabled. This

will apply in every instance except in the event the high

pressure switch is tripped or emergency shutdown then the

compressor output will be disable immediately.

Compressor Short Cycle Delay Time

The compressor short cycle time delay will ensure that the

compressor output will not be enabled for a minimum of

(5) minutes after it is disabled. This allows for the system

refrigerant pressures to equalize after the compressor is

disabled.

Optional FX10 Microprocessor Control cont.

Advertising