ENVISION 7-25 TONS INSTALLATION MANUAL

37

Multistate Input (Type 13)

13:1 Effective Occupancy

[Read, shows the occupancy status of the heat

pump. 1=Occupied, 2=Unoccupied, 3=Bypass

(temporary

occupancy)]

13:2 Mode

[Read, shows heat pump as normal or emergency

shutdown 1=Auto(normal), 7=Off(shutdown)]

13:3 Compressor/Blower Prove

[Read, shows the contact status of BI-4.]

Multistate Output (Type 14)

14:1 Occupancy Command

[Read/Write, controls the occupancy mode of the

heat Pump. 1=Occupied, 2=Unoccupied, 3=Bypass

(Temporary Occupancy), 4=Standby,

255=Uncommanded]

14:2 Blower Command (G)

[Read/Write, network command to run the blower]

14:3 Comp1 Command (Y1)

[Read/Write, network Y1 command (compressor

1

call).]

14:4 Comp2 Command (Y2)

[Read/Write, network Y2 command (compressor

2

call).]

14:5 Rev Vlv Cmd (O)

[Read/Write, network O command. 1= heating,

2=

cooling.]

14:6 Emergency Override

[Read/Write, provide means of emergency

shutdown]

14:7 Alarm Reset

[Read/Write, allows remote reset of manual reset

alarms, Command to a ‘2’ value for reset action,

1 for normal Operation.]

14:8 BO5 ElectHeat

[Read/Write, network command to enable electric

heat (interlocked with BI4)]

14:9 BO9 Spare

[Read/Write, network command to enable/disable

BO9]

Optional FX10 Microprocessor Control - BACnet Variables cont.