Da c e, Nlv180 - blower performance data – WaterFurnace Envision (XL) User Manual

Page 19

Advertising
background image

ENVISION 7-25 TONS INSTALLATION MANUAL

20

Airflow in CFM with dry coil and clean air filter.

External Static Pressure (in. w.g.)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.2

1.4

1.6

1.8

2.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

4.0

4.0

BHP

0.61

0.64

0.66

0.68

0.76

0.81

0.87

0.89

0.94

1.05

RPM

581

601

621

663

703

739

774

784

827

867

TURNS OPEN

5.0

4.5

4.0

3.0

2.0

1.5

1.0

0.5

2.0

1.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

4.0

4.0

BHP

0.64

0.66

0.71

0.77

0.82

0.85

0.94

0.97

1.04

1.14

RPM

591

611

642

682

712

740

778

795

841

886

TURNS OPEN

4.5

4.0

3.5

2.5

1.5

1.0

0.5

0.0

1.5

0.5

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

4.0

4.0

4.0

BHP

0.65

0.66

0.68

0.75

0.86

0.87

0.88

1.02

1.05

1.14

1.23

RPM

580

600

621

662

701

722

742

782

805

855

905

TURNS OPEN

5.0

4.5

4.0

3.0

2.0

1.5

1.0

0.0

2.5

1.5

0.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

5.0

5.0

BHP

0.69

0.70

0.76

0.86

0.92

0.93

1.01

1.08

1.11

1.19

1.30

0.74

0.80

0.85

RPM

590

610

641

681

711

731

761

790

809

850

898

470

480

496

TURNS OPEN

4.5

4.0

3.5

2.5

1.5

1.0

0.5

0.0

3.0

2.5

2.0

1.0

3.0

2.5

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

BHP

0.72

0.73

0.74

0.84

0.96

0.98

0.99

1.13

1.14

1.17

1.23

1.36

1.48

1.59

1.69

RPM

579

600

620

660

700

721

741

780

797

813

845

890

940

960

991

TURNS OPEN

5.0

4.5

4.0

3.0

2.0

1.5

1.0

0.0

3.0

2.5

2.0

1.0

0.0

3.0

2.5

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

5.0

5.0

5.0

BHP

0.76

0.77

0.84

0.95

1.02

1.04

1.12

1.20

1.23

1.27

1.36

1.49

1.58

1.72

1.86

RPM

589

609

640

680

710

730

760

788

808

828

868

914

941

963

991

TURNS OPEN

4.5

4.0

3.5

2.5

1.5

1.0

0.5

0.0

2.5

2.0

1.5

0.5

3.5

2.5

2.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

5.0

BHP

0.79

0.80

0.82

0.93

1.06

1.08

1.10

1.25

1.26

1.31

1.36

1.49

1.62

1.67

1.85

2.03

RPM

578

599

619

659

699

719

739

778

795

819

843

890

937

942

967

991

TURNS OPEN

5.0

4.5

4.0

3.0

2.0

1.5

1.0

0.0

3.0

2.5

2.0

1.0

0.0

3.0

2.5

2.0

Bold Face Requires Larger 2.0 HP Motor

A=Std Static/Std Mtr;B=Low Static/Std. Mtr;C=High Static/Std. Mtr;D=Std Static/Large Mtr;E=High Static/Large Mtr

Units factory shipped with standard static sheave and drive at 3 turns open (5600 cfm @ 0.6 in. ESP). Other speeds require field selection.

ISO/AHRI rating point with standard static sheave and drive at 1.5 turns open (5600 cfm @ 0.7 in. ESP). Other speeds require field selection.

For applications requiring higher static pressures, contact your local representative.

Performance data does not include drive losses and is based on sea level conditions.

Do not operate in gray region. "na" = information not available at time of printing.

All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.

For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).

Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, and 400 fpm by 0.12 in. wg.

BHP is given for each blower. Multiply BHP x 2 for unit BHP.

7/25/07

5800

6000

6200

6400

Rated CFM

5200

5400

5600

D

A

C

E

NLV180 - Blower Performance Data

Belt Drive