2 removing an electronic module, 3 changing an electronic module during operation, Removing an electronic module – Pilz PSSu E F 4DI User Manual

Page 19: Changing an electronic module during operation

Advertising
background image

Installation

Operating Manual PSSu E F 4DI(­T)(­R)
21310­EN­05

19

5.3.2

Removing an electronic module

Procedure:

}

Press the locking mechanisms [1] together simultaneously.

}

Pull out the electronic module [2].

Schematic representation:

[1]

[2]

[1]

5.3.3

Changing an electronic module during operation

It is possible to change an electronic module during operation. The configuration data is re­
tained when a module is changed.

Effects:

}

System environment A:

}

In the event of a potential FS communication error, the FS section of the PSSu system
and all relevant I/O­Groups (SafetyBUS p) switch to a STOP condition.

}

System environment B:

}

All FS hardware outputs on the PSSu system switch to a safe condition.

The substitute values are used for the modules' FS outputs, with Valid Bits =
FALSE.

CAUTION!

Sparking can cause interference and errors!

Only change the module when the load is switched off!

Advertising
This manual is related to the following products: