Wiring

Operating Manual PSSu E F 4DI(­T)(­R)
21310­EN­05

21

21

11

[1]

[3]

[2]

[4]

[5]

[6]

Please note:

}

The minimum cable cross section for field connection terminals on the base modules is
0.14 mm

(AWG26).

}

The maximum cable cross section for field connection terminals is:

Digital inputs: 1.5 mm

2

 (AWG16)

Digital outputs: 2.0 mm

2

 (AWG14)

Inputs/outputs on the counter modules: 1.5 mm

2

 (AWG16)

Analogue inputs/outputs: 1.5 mm

2

 (AWG16)

Communication cables: 1.5 mm

2

 (AWG16)

Test pulse outputs: 1.5 mm

2

 (AWG16)

Power supply: 2.5 mm

2

 (AWG12)

Functional earth: 2.5 mm

2

 (AWG12)

}

On base modules with screw terminals:

If you use a multi­strand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm

2

, Form A or C,

although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 60947­1, such as the PZ 1.5 or PZ 6.5 from
Weidmüller, for example.

Maximum torque setting: 0.8 Nm