Pilz PSSu E F 4DI User Manual

Page 31

Advertising
background image

Technical details

Operating Manual PSSu E F 4DI(­T)(­R)
21310­EN­05

31

Inputs

312200

314200

315200

Max. processing time of
input when signal
changes from "1" to "0"

1,000 ms

1,000 ms

1,000 ms

Max. processing time of
input when signal
changes from "0" to "1"

1,000 ms

1,000 ms

1,000 ms

Min. processing time of in­
put when signal changes
from "1" to "0"

0,50 ms

0,50 ms

0,50 ms

Min. processing time of in­
put when signal changes
from "0" to "1"

0,50 ms

0,50 ms

0,50 ms

Potential isolation
between input and internal
module bus voltage

Yes

Yes

Yes

Test pulse outputs

312200

314200

315200

Number of test pulse out­
puts

2

2

2

Voltage, test pulse out­
puts

24 V DC

24 V DC

24 V DC

Short circuit­proof

Yes

Yes

Yes

Number of outputs that
can be configured as test
pulses

2

2

2

Max. output current at "1"
signal

0,25 A

0,25 A

0,25 A

Max. cable length
between test pulse output
and input

200 m

200 m

200 m

Standard for voltage inter­
ruptions

EN61131­2, EN61496­1

EN61131­2, EN61496­1

Environmental data

312200

314200

315200

Application site

In accordance with the
standard

EN 50125­3

Application site

Track area (1 m ­ 3 m)

In accordance with the
standard

EN 61373

Application site

Category 1, Class A + B

Climatic suitability

EN 60068­2­1, EN
60068­2­14, EN
60068­2­2, EN
60068­2­30, EN
60068­2­78

EN 60068­2­1, EN
60068­2­14, EN
60068­2­2, EN
60068­2­30, EN
60068­2­78

EN 50125­1, EN 50125­3,
EN 50155, EN 60068­2­1,
EN 60068­2­14, EN
60068­2­2

Advertising
This manual is related to the following products: