7 operation, 1 messages, Section 7 – Pilz PSSu E F 4DI User Manual

Page 28: Operation, Messages, 7operation

Advertising
background image

Operation

Operating Manual PSSu E F 4DI(­T)(­R)
21310­EN­05

28

7

Operation

7.1

Messages

A module error is displayed via the "Err" LED (see section entitled "Display elements"), sig­
nalled to the head module and then entered in the head module's

}

Error stack, with PSSu in system environment A

}

Diagnostic log, with PSSu in system environment B.

The module can detect the following errors:

Module error

Explanation

Remedy

Start­up error

Error as the PSSu system starts
up

Change faulty module.

Configuration error

Incorrect module type configured.

The configured hardware registry
does not match the actual hard­
ware registry.

FS communication error

Error during FS communication

Change faulty module.

Bus termination error

There is no terminating plate or
there is a bad contact with the
module bus.

Install a terminating plate with in­
tegrated end bracket or insert the
base modules together correctly.

Temperature error: too warm

Ambient temperature too high:
Error stack entry/diagnostic log
entry

Ensure there is sufficient ventila­
tion in the control cabinet or pre­
vent overload.

Error in the feedback loop

FS input detects an error in the
feedback loop or FS input is de­
fective.

Check FS input, check the config­
uration of the feedback loop,
check the signals, or check the
wiring and contacts.

Input error

Error during the cyclical input test.
Possible cause: Input defective.

Change faulty module.

Test pulse error

Possible causes: Short circuit
between a test pulse and a supply
voltage, or a defective module.

Rectify the short circuit or change
the faulty module.

Advertising