1 safety characteristic data, Safety characteristic data – Pilz PSSu E F 4DI User Manual

Page 33

Advertising
background image

Technical details

Operating Manual PSSu E F 4DI(­T)(­R)
21310­EN­05

33

Environmental data

312200

314200

315200

Supply interruptions

In accordance with the
standard

–

–

EN 50155

Class

–

–

S2, C1, C2

Max. operating height
above sea level

2000 m

5000 m

2000 m

Airgap creepage

In accordance with the
standard

EN 60664­1

EN 60664­1

EN 50124­1

Overvoltage category

II

II

OV2

Pollution degree

2

2

PD1

Protection type

In accordance with the
standard

EN 60529

EN 60529

EN 60529

Mounting area (e.g.
control cabinet)

IP54

IP54

IP51

Housing

IP20

IP20

IP20

Terminals

IP20

IP20

–

Mechanical data

312200

314200

315200

Material

Bottom

PC

PC

PC

Front

PC

PC

PC

Coding

PA

PA

PA

Mounting type

plug­in

plug­in

plug­in

Dimensions

Height

76,0 mm

76,0 mm

76,0 mm

Width

12,6 mm

12,6 mm

12,6 mm

Depth

60,2 mm

60,2 mm

60,2 mm

Weight

44 g

45 g

45 g

Mechanical coding

Type

D

D

D

Colour

Yellow

Yellow

Yellow

The standards current on 2009­10 apply.

8.1

Safety characteristic data

Operating
mode

EN ISO
13849­1:
2008

PL

EN ISO
13849­1:
2008

Category

EN IEC
62061

SIL CL

EN IEC
62061

PFH

D

 [1/h]

IEC 61511

SIL

IEC 61511

PFD

EN ISO
13849­1:
2008

T

M

 [year]

1­channel

PL d

Cat. 2

SIL CL 2

9,10E­09

SIL 2

7,25E­04

20

2­channel

PL e

Cat. 3

SIL CL 3

3,10E­09

SIL 3

1,85E­05

20

1­ch., pulsed
light barrier

PL e

Cat. 4

SIL CL 3

2,91E­09

SIL 3

7,52E­05

20

If the module is operated at an ambient temperature above 60° C, the values stated in the
table for PFH

D

 and PFD will need to be doubled when a safety function is calculated.

Advertising
This manual is related to the following products: