Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-1

6.1

General wiring guidelines

6

Wiring

6

6000

Wiring

Wiring

6-

6.1

General wiring guidelines

6100

General wiring guidelines

6-

][Verdrahtung BA Einleitung

Please note:

][Verdrahtung ST-Ausgang

The actuators may be connected using unshielded cables.

The outputs do not need suppression for inductive loads.

Use copper wiring.

][Verdrahtung Zusatz mit C

The terminal configuration as stated on the front plate applies for base

modules with C-rail. The terminal configuration as stated in the tech-

nical documentation applies for all other base modules.

6.1.1

Mechanical connection of the base modules

Mechanical connection of the base modules

6-

][Modulverdrahtung mech

Procedure:

Use a flat blade screwdriver (DIN 5264-A)!

Strip the wire back 8 mm.

If necessary, label the connection level with a colour marker [3].

Base module with screw terminals:

– Use a screwdriver to loosen the screw on the screw terminal [1]

– Insert the stripped cable into the round fixing hole [2], as far as it

will go.

– Tighten up the screw on the screw terminal.

– Check that the cable is firmly seated.

Base module with cage clamp terminals:

– Insert the screwdriver [4] into the square hole [1].

– Insert the stripped cable into the round fixing hole [2], as far as it

will go [5].

– Pull out the screwdriver [6].

– Check that the cable is firmly seated.

DIN 5264-A