Terminal configuration, 6wiring, 2 terminal configuration – Pilz PSSu E S 2DO 2-T User Manual

Page 27

Advertising
background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-3

6.2

Terminal configuration

6

Wiring

6.2

Terminal configuration

6200

Terminal configuration

6-

][Klemmenbelegung 2DO

Base module

Terminal configuration

Screw terminals:
PSSu BP 1/8S
PSSu BP 1/8S-T

Cage clamp terminals:
PSSu BP 1/8C
PSSu BP 1/8C-T

Without C-rail:

11: Output O0

21: Output O1

12-22: 0 V periphery supply
(12-22 linked within the base module)

13-23: 0 V periphery supply
(13-23 linked within the base module)

14: Not connected

24: Not connected

Screw terminals:
PSSu BP-C 1/8S
PSSu BP-C 1/8S-T

Cage clamp terminals:
PSSu BP-C 1/8C
PSSu BP-C 1/8C-T

With C-rail:

11: Output O0

21: Output O1

12-22: 0 V periphery supply
(12-22 linked within the base module)

13-23: C-rail supply
(13-23 linked within the base module)

14: Not connected

24: Not connected

Screw terminals:
PSSu BP-C1 1/12S
PSSu BP-C1 1/12S-T

Cage clamp terminals:
PSSu BP-C1 1/12C
PSSu BP-C1 1/12C-T

With C-rail:

11: Output O0

21: Output O1

12-22: 0 V periphery supply
(12-22 linked within the base module)

13-23: C-rail supply
(13-23-16-26 linked within the base
module)

14: Not connected

24: Not connected

15-25: 0 V periphery supply
(15-25 linked within the base module)

16-26: C-rail supply
(13-23-16-26 linked within the base
module)

21

11

22

12

23

13

24

14

21

11

22

12

23

13

24

14

21

11

22

12

23

13

24

14

26

16

25

15

Advertising