Installation – Desa FPVF33PRA User Manual

Page 15

Advertising
background image

www.desatech.com

113109-01C

15

2. Remove screws that attach log base assembly

to fireplace (see Figure 23). Carefully lift up

log base assembly and remove from fireplace

(see Figure 23).

Note:

If adding the G8005 series brick liner acces-

sory, install it now. Follow instructions in G8005

accessory kit.

CAUTION: Do not pick up

log base assembly by burner.

This could damage burner. Only

handle base by grates.

3. Route gas line (provided by installer) from

equipment shutoff valve to fireplace. Route

flexible gas supply line through one of the

access holes.

NOTICE: Most building codes

do not permit concealed gas

connections. A flexible gas line

is provided to allow accessibility

from the fireplace (see Figure 24).

The flexible gas supply line con-

nection to the equipment shutoff

valve should be accessible.

4. Attach the flexible gas line to gas supply (see

Figure 24). Check tightness of flexible gas

line attached to gas regulator of fireplace (see

Figure 24).

5. Check all gas connections for leaks. See

Checking Gas Connections.

INSTALLATION

Continued

Figure 23 - Removing Log Base

Assembly From Fireplace

Figure 24 - Attaching Flexible Gas Lines

Together

Flexible Gas Line
from Fireplace
Gas Regulator

To Fireplace Gas
Regulator

Equipment Shutoff Valve
Provided by Installer

Propane/LP
To External
Regulator

Natural Gas
To Gas Meter

6. Replace log base assembly back into fireplace.

Feed flexible gas line into fireplace base area

while replacing log base assembly. Make sure

the entire flexible gas line is in fireplace base

area. Reattach log base assembly to fireplace

with screws removed in step 2.

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak detec-

tion fluid to all joints. Bubbles

forming show a leak. Correct all

leaks at once.

CAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply and

fireplace. See guidelines under

Connecting Fireplace to Gas

Supply, page 14.

pRESSURE TESTING GAS SUppLY
pIpING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1. Disconnect fireplace with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply piping system.

Pressures in excess of 1/2 psig will damage

fireplace regulator.