Configuration of sntl300-p via rs485 – Computronic Controls Sentinel 300P User Manual

Page 20

Advertising
background image

SNTL300P-PCSUITE installation & operation

ci0042 p20/22 issue 5 2015-04-22

Configuration of SNTL300-P via RS485

In order for customers to transmit their own remote profiles to the SNTL300P, the following protocol must be
used:

Packet must be sent in MODBUS RTU format.

Use the ‘Set multiple holding registers’ command (0x10)

Slave address must equal that of the charger. (Default of 100)

Register start address = 64

Number of points = 17

Register

SNTL300P Function

Scaling

40064

Float voltage

Voltage X 10

40065

Boost voltage

Voltage X 10

40066

Boost initiate voltage

Voltage X 10

40067

Boost period

Minutes

40068

Low alarm voltage

Voltage X 10

40069

High alarm voltage

Voltage X 10

40070

Number of cells

Cells X 1

40071-40080

Profile name

2 ASCII characters per register