Configuration of SNTL150-P via TTL

In order for customers to transmit their own remote profiles to the SNTL150P, the following protocol must be
used:

Packet must be sent in the following format

[Byte1] Node Address must be that of the charger (Preset of 100)

[Byte2] Write Multiple Registers (0x10)

[Byte3] Starting Address (High Byte)

[Byte 4] Starting Address (Low Byte)

[Byte 5] Number of Registers {High Byte)

[Byte 6] Number of Registers (Low Byte)

[Bytes 7 – 20] Data as per below

Register start address = 11

Number of points = 7

Register

SNTL150P Function

Scaling

40011

Float voltage

Voltage X 10

40012

Boost voltage

Voltage X 10

40013

Boost initiate voltage

Voltage X 10

40014

Boost period

Minutes

40015

Low alarm voltage

Voltage X 10

40016

High alarm voltage

Voltage X 10

40017

(High Byte) Number of cells

Cells X 1

(Low Byte is reserved, the value stored
must be read and then rewritten to
SNTL150P when updating profile)

The confirmation message back will match Bytes 1

– 6 of transmitted message. Changes are made instantly.