ATEIS DIVA8G2 User Manual

Page 164

Advertising
background image

DIVA system

164

© 2012 ATEÏS

FigAnnexe 1

In this case, the measurement unit can only detect 0V (closed) or 4.4 V (opened).

In order to have different state measurement like open line and short-circuit we need to add a resistor
network to the end of the line, see picture below.

FigAnnexe 2

Using the resistor Network, the measurement unit can detect 4 different states: 1.3 V, 2 V, 2.7 V and
4.4 V. The 4 states correspond respectively to Shortcut, Closed Contact, Opened contact and Absent
(open line).

According to the FigAnnexe 2, you have a fully monitored line responding to the security norms.