Basic system communications checklist – Auto-Zone Control Systems Auto-Zone Basic Systems Installation & Operation (Version 02C) User Manual

Page 109

Advertising
background image

Auto-Zone Basic

Section

4

Start-Up & Troubleshooting

4-7

Basic System
Communications Checklist

Basic System without Optional CommLink

‰ Zone Manager is correctly addressed as 0
‰ Zone Controllers are correctly addressed from 1 to 16
‰ Power has been cycled after changing addresses
‰ There are no duplicate addresses on the loop
‰ The first Zone Controller on the communication loop is connected to the

Zone Manager communication terminal

‰ All communication wiring is landed correctly, T to T, R to R, and SHLD to SHLD
‰ All Zone Controllers are wired to 24 Volt AC power supply
‰ Zone Manager is wired to 24 Volt AC power supply
‰ All 24 VAC power wiring is landed correctly - 24VAC to 24VAC and GND to GND
‰ Zone Manager is powered up
‰ Zone Controllers are powered up

Additional Checks for Basic System with
Optional CommLink IV

‰ CommLink IV is connected to the communications loop
‰ CommLink IV is set for single loop operation
‰ Zone Manager is correctly addressed as 17
‰ CommLink IV is wired to 24 Volt AC power supply
‰ CommLink IV is powered up

Other Optional Equipment

‰ Computer is correctly connected to the CommLink IV
‰ Prism™ software is installed on a computer
‰ Remote Link II is correctly connected to the CommLink IV
‰ Remote Link II is connected to a working phone line
‰ Second Remote Link II is connected to a computer and working phone line off-site
‰ IP Module is correctly installed in the CommLink IV
‰ CommLink IV with installed IP Module is connected to an Ethernet router for off-site

communications