Section 4

Auto-Zone Basic

4-36

Start-Up and Troubleshooting

Step 2

Measure the voltage at the suspect Zone Controller terminals with the Communications
Loop disconnected form the Zone Controller.




Basic System - Without Optional

CommLink Installed

Basic System - With Optional

CommLink Installed

Measure Voltage Measure Voltage

T to SHLD

+ 2.5 to 2.4 VDC

T to SHLD

+ 2.5 to 2.4 VDC

R to SHLD

+ 2.5 to 2.4 VDC

R to SHLD

+ 2.5 to 2.4 VDC

If the voltages are not within the specified voltage ranges, the Zone Controller communi-
cation driver chip is probably damaged and will require replacement. If the measured
voltages are within the specified voltage range, the Zone Controller driver chip is not
damaged and the problem is related to another part of the loop. Repeat Zone Controller
troubleshooting Steps 1 & 2 for each controller on the loop to determine which one is
causing the problem. If you have a CommLink (optional) installed, please see the
CommLink Troubleshooting Section of this manual.

T

SHLD

R

COMM

LOOP

+

-

T

R

SHLD

+

-

T

SHLD

R

COMM

LOOP

+

-

T

R

SHLD

+

-

Measuring R to SHLD

Measuring T to SHLD