Setpoint screen #3, Setpoint screen #4, Setpoint screen #5 – Auto-Zone Control Systems Auto-Zone Basic Systems Installation & Operation (Version 02C) User Manual

Page 86: Auto-zone basic

Advertising
background image

Section 3

Auto-Zone Basic

3-18 Programming

Setpoint Screen #3


Minimum

Default

Maximum

Cool Staging

1 Min

4 Min

30 Min

Min Cool Off

1 Min

4 Min

30 Min

Heat Staging

1 Min

4 Min

30 Min

Min Heat Off

1 Min

4 Min

30 Min

Setpoint Screen #4

Minimum

Default

Maximum

Interval

1 Min

10 Min

30 Min

Setpoint Screen #5



Minimum

Default

Maximum

Closed Volts

0.0 VDC

0.0 VDC

10.0 VDC

Opened Volts

0.0 VDC

10.0 VDC

10.0 VDC

The heating and cooling stages must have been off for a
minimum amount of time before they can be activated or re-
activated. As each additional stage of heating or cooling is
added, a minimum Staging Delay period must be satisfied
between each additional stage required.

Cool Staging: 4 Min

Min Cool Off: 4 Min

Heat Staging: 4 Min

Min Heat Off: 4 Min

If the Zone Manager needs to change HVAC modes
between heating and cooling, a Changeover Delay time
must be satisfied first. This prevents "chasing" due to
alternate hot and cold air always being supplied to the
zones after short intervals.

Manager Setpoints

Heat/Cool Changeover

Interval....: 15 Min

If the Zone Manager has been configured for Economizer
Control
, this screen will appear. You can set the voltages
required to open and closed the damper. Some actuators use a
2-10 VDC signal instead of 0-10 VDC.

If the system is not configured for Economizer Control, no
economizer setpoint screens will appear.

Economizer Setpoints

Closed Volts: 0.0

Opened Volts: 10.0