2 ep1098 - technical data, 3 ep1098-0001 - process image – BECKHOFF EP1xxx User Manual

Page 15

Advertising
background image

Product overview

2.4.2

EP1098 ­ Technical Data

Technical data

EP1098­0001

Fieldbus

EtherCAT

Fieldbus connection

2 x M8 socket (green)

Number of inputs

8 (negative switching)

Input connections

M8

Nominal input voltage

24 V

DC

 (­15%/+20%)

Input filter

10 µs

"0" signal voltage

11…30 V

"1" signal voltage

0…7 V

Input current

typically 2.5 mA (EN 61131­2, Type 3)

Module electronic supply

derived from control voltage Us

Module electronic current
consumption

typically 120 mA

Sensor supply

derived from control voltage, Us

Sensor current consumption

max. 0.5 A total, short­circuit proof

Power supply connection

Feed: 1 x M8 plug, 4­pin
Onward connection: 1 x M8 socket, 4­pin

Process image

8 input bits

Electrical isolation

Control voltage/fieldbus: yes

Permissible ambient temperature
during operation

­25°C ... +60°C
0°C ... +55°C (according to cULus, see UL Requirements)

Permissible ambient temperature
during storage

­40°C ... +85°C

Vibration / shock resistance

conforms to EN 60068­2­6 / EN 60068­2­27

EMC resistance/emission

conforms to EN 61000­6­2 / EN 61000­6­4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Installation position

variable

Approvals

CE, cULus