3 power cables, 4 power cable conductor losses – BECKHOFF EP1xxx User Manual
Page 44
![background image](/files/774920/content/doc044.png)
Mounting and cabling
3.3.3
Power cables
Ordering data
Order designation
Power lead
Screwin
connector
Contacts
Crosssection Length
ZK202032000020
Straight socket, open end
M8
4pin
0.34 mm
2
2.00 m
ZK202032000050
5.00 m
ZK202032000100
10.00 m
ZK202034000020
Angled socket, open end
2.00 m
ZK202034000050
5.00 m
ZK202034000100
10.00 m
ZK202031320001
Straight socket, straight
socket
0.15 m
ZK202031320005
0.50 m
ZK202031320010
1.00 m
ZK202031320020
2.00 m
ZK202031320050
5.00 m
ZK202033340001
Angled socket, angled
socket
0.15 m
ZK202033340005
0.50 m
ZK202033340010
1.00 m
ZK202033340020
2.00 m
ZK202033340050
5.00 m
Further available power cables may be found in the Beckhoff catalog or on our internet pages (
www.beckhoff.com).
Technical data
Technical data
Rated voltage according to IEC60 6641
60 V
AC
/ 75 V
DC
Contamination level according to IEC 60 6641
3/2
Insulation resistance IEC 60 5122
>10
9
W
Current carrying capacity according to IEC 605123
4 A
Volume resistance according to IEC 605122
< 5 mW
Protection class according to IEC 60529
IP65/66/67, when screwed together
Ambient temperature
30°C to +80°C
3.3.4
Power cable conductor losses
The ZK2020xxxxyyyy power cables should not exceed the total length of 15 m at 4 A (with continuation).
When planning the cabling, note that at 24 V nominal voltage, the functionality of the module can no longer
be assured if the voltage drop reaches 6 V. Variations in the output voltage from the power supply unit must
also be taken into account.
EP1xxx
44
Version 2.1.0