2 ep1816-0008 - technical data, 3 ep1816-0008 - status-leds – BECKHOFF EP1xxx User Manual

Page 27

Advertising
background image

Product overview

2.8.2

EP1816­0008 ­ Technical Data

Technical data

EP1816­0008

Fieldbus

EtherCAT

Fieldbus connection

2 x M8 socket (green)

Number of inputs

14

Input connections [

}

 50]

25 pin SUB­D socket

Nominal input voltage

24 V

DC

 (­15%/+20%)

Input filter

10 µs

"0" signal voltage

­3...+5 V (EN 61131­2, Type 3)

"1" signal voltage

+11...+30 V (EN 61131­2, Type 3)

Input current

typically 3 mA (EN 61131­2, Type 3)

Module electronic supply

derived from control voltage Us

Module electronic current consumption

typically 120 mA

Sensor supply

derived from control voltage Us

Sensor current consumption

max. 0.5 A total, short­circuit proof

Power supply connection

Feed: 1 x M8 plug, 4­pin
Onward connection: 1 x M8 socket, 4­pin

Process image

16 input bits

Electrical isolation

Control voltage/fieldbus: yes

Permissible ambient temperature during operation

­25°C ... +60°C
0°C ... +55°C (according to cULus, see UL
Requirements)

Permissible ambient temperature during storage

­40°C ... +85°C

Vibration / shock resistance

conforms to EN 60068­2­6 / EN 60068­2­27

EMC resistance/emission

conforms to EN 61000­6­2 / EN 61000­6­4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Installation position

variable

Approvals

CE, cULus

2.8.3

EP1816­0008 ­ Status­LEDs

Fig. 16: EP1816­0008 ­ Status­LEDs

LED display

LED

Display

Meaning

STATUS 1­8

Green illuminated

A signal (24 V) is present at a least one of the inputs for
channels 1 to 8

STATUS 9­16

Green illuminated

A signal (24 V) is present at a least one of the inputs for
channels 9 to 16

Us

off

The power supply voltage, Us, is not present

Green illuminated

The power supply voltage, Us, is present

Up

off

The power supply voltage, Up, is not present

Green illuminated

The power supply voltage, Up, is present

EP1xxx

27

Version 2.1.0

Advertising