2 ep1111-0000 - technical data, 3 ep1111-0000 - process image – BECKHOFF EP1xxx User Manual

Page 18

Advertising
background image

Product overview

2.5.2

EP1111­0000 ­ Technical Data

Technical data

EP1111­0000

Fieldbus

EtherCAT

Fieldbus connection

2 x M8 socket (green)

Task within EtherCAT system

identification of any EtherCAT group in the EtherCAT
network

Number of ID switches

3

Positions per ID switch

10

Number of different IDs

999

Module electronic supply

derived from control voltage Us

Module electronic current consumption

typically 120 mA

Sensor supply

derived from control voltage, Us

Sensor current consumption

max. 0.5 A total, short­circuit proof

Power supply connection

Feed: 1 x M8 plug, 4­pin
Onward connection: 1 x M8 socket, 4­pin

Process image

2 byte input data

Weight

app. 165 g

Permissible ambient temperature during operation

­25°C ... +60°C
0°C ... +55°C (according to cULus, see UL
Requirements)

Permissible ambient temperature during storage

­40°C ... +85°C

Vibration / shock resistance

conforms to EN 60068­2­6 / EN 60068­2­27

EMC resistance/emission

conforms to EN 61000­6­2 / EN 61000­6­4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Installation position

variable

Approvals

CE, cULus

2.5.3

EP1111­0000 ­ Process image

ID inputs

You will find input data of the ID switches under under ID Inputs.

Fig. 9: EP1111­0000, ID inputs

EP1xxx

18

Version 2.1.0