3 ep1809, ep1819 - technical data, 4 ep1809-0021 - process image – BECKHOFF EP1xxx User Manual

Page 24

Advertising
background image

Product overview

2.7.3

EP1809, EP1819 ­ Technical data

Technical data

EP1809­0021

EP1809­0022

EP1819­0022

Fieldbus

EtherCAT

Fieldbus connection

2 x M8 socket (green)

Number of inputs

16

Input connections

M8

M12

M12

Nominal input voltage

24 V

DC

 (­15%/+20%)

Input filter

3 ms

3 ms

10 µs

"0" signal voltage

­3...+5 V (similar to EN 61131­2, Type 3)

"1" signal voltage

+11...+30 V (similar to EN 61131­2, Type 3)

Input current

typically 3 mA (similar to EN 61131­2, Type 3)

Module electronic supply

derived from control voltage Us

Module electronic current
consumption

typically 130 mA (without sensor current)

Sensor supply

derived from control voltage Us

Sensor current consumption

max. 0.5 A total, short­circuit proof

Power supply connection

Feed: 1 x M8 plug, 4­pin
Onward connection: 1 x M8 socket, 4­pin

Process image

16 input bits

Electrical isolation

Control voltage / fieldbus: yes

Permissible ambient temperature
during operation

­25°C ... +60°C

­25°C ... +60°C
0°C ... +55°C (according to
cULus, see UL Requirements)

­25°C ... +60°C

Permissible ambient temperature
during storage

­40°C ... +85°C

Vibration / shock resistance

conforms to EN 60068­2­6 / EN 60068­2­27

EMC resistance / emission

conforms to EN 61000­6­2 / EN 61000­6­4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Installation position

variable

Approvals

CE

CE, cULus

CE

2.7.4

EP1809­0021 ­ Process image

Channel 1 to Channel 16

You will find the 16 digital inputs to the module (here using the EP1809­0021 as an example) under Channel
1 to Channel 16.

EP1xxx

24

Version 2.1.0