5 Installation

BECKHOFF

Drive Technology

34

Version : 4.6

AX5000

5.2.1.3

External protection, UL-compliant

Integral solid state short circuit protection does not provide branch circuit protection. Branch

circuit protection must be provided in accordance with the Manufacture Instructions, National

Electrical Code and any additional local codes.

Suitable for use on a circuit capable of delivering not more than 18000 rms symmetrical

amperes, 480 V maximum, when protected by RK5 class fuses.

For alternatives regarding class RK5 UL-fuses, you must observe “UL508 A, chapter

SB4.2.3, exception no. 1”. For further questions regarding UL-fuses, please contact your

responsible certification authority.

Single-phase

Fusing

AX5101 AX5103 AX5106 AX5201 AX5203 AX5206

AC supply (max.)

*)

6 A

12 A

20 A

12 A

20 A

20 A

24 V supply (max.)

3 A

Brake resistor

electronic

*) UL-Mains fuses must be used.
Three-phase

Fusing

AX

5101 5103 5106 5112 5118 5125 5140 5201 5203 5206

AC suppl (max.)

*)

6 A 12 A 20 A 20 A 35 A 45 A 80 A 12 A 20 A 20 A

24 V supply (max.)

3 A

Brake resistor

elektronisch

*) UL-Mains fuses must be used.

When protected by RK5 class fuses:


AX5112
Rated 20 A, min. 480 V

AX5118
Rated 35 A, min. 480 V

AX5125
Rated 45 A, min. 480 V

AX5140
Rated 80 A, min. 480 V


5.2.1.4

Internal protection, UL-compliant

Circuit

Fuse

24 V - system voltage

3.4 AF

24 V - peripheral voltage

electronic

Brake resistor

electronic