5 Installation

AX5000

Version : 4.6

37

5.2.3.1

Connection example - module AX5901 and AX5911 (AX Bridge)

This connection option enables a safe system to be set up very quickly. The modules are

attached to plug contacts X01, X02 and X03, the relevant slides are pushed to the left and

screwed tight. According to CE the current carrying capacity of power busbars of the

AX Bridge is limited to 85 A.

CAUTION

Hazard to inviduals through electric shock
Move all busbar sliders to the left limit stop in order to ensure full current

carrying capacity. Then tighten all screws with a torque of 2.2 Nm.

CAUTION

Hazard to inviduals and equipment
Please ensure that the connection line for the AX5901 supply module is

adequately dimensioned. The dimensioning depends on the total rated

current and must comply with EN60204-1.

The supply connection is established as described in sections 5.2.1 and 5.2.2.

Information of the terminal points

Terminal points

Conductor design

max. Conductor

cross-section

Tightening torque

L1-L3, PE

single wire

10 mm

2

2,2 Nm

L1-L3, PE

flnely stranded with

wire end sleeves

16 mm

2

2,2 Nm

L1-L3, PE

flnely stranded /

stranded

25 mm

2

2,2 Nm