2 24 vdc - supply network connection (x03) – BECKHOFF AX5000 1,5 A - 40 A User Manual

Page 36

Advertising
background image

5 Installation

BECKHOFF

Drive Technology

36

Version : 4.6

AX5000

5.2.2

24 V

DC

- supply network connection (X03)

The 24 V

DC

connection

"X03" is used for supplying control electronics and periphery with

DC voltage. The control electronics and the periphery can be supplied separately with two

different voltage sources.

Note

If one transformer is used for the 24 V

DC

power supply, the connections U

S

and U

P

must be bridged, in order to ensure that both the control electronics

and the periphery are supplied.

Supply through via one transformer

Supply via two transformers

5.2.3

Connection of several servo drives to form a drive system

Drive system with UL-Listing!
Please note the configuration example in chapter 5.2.4

Attention

Hazard to the equipment

The connection sequence of the devices is not arbitrary. The total rated

current of the device must decrease from the power supply.

AX5112-AX5203-AX5106-AX5201

= OK; AX5201-AX5112-AX5203 ≠ OK

All devices in a drive system are always to be disconnected from and

reconnected to the mains supply together (emergency stop, mains

contactor etc.).

CAUTION

Danger for persons and equipment
Note the total rated current of the connected devices.

According to CE the current carrying capacity of power busbars of the

AX Bridge is limited to 85 A.

Attention

Destruction of the external brake resistor
An external brake resistor may not be connected to the X02 terminal point

(DC link) in a drive system. Use an external brake module AX5021 for this.

Advertising