5 Installation
BECKHOFF
Drive Technology
38
Version : 4.6
AX5000
5.2.3.2
Connection example - wiring in series without AX Bridge
Wire the relevant connections using individual cables.
CAUTION
Hazard to inviduals and equipment
•
Please ensure that the final supply network connection cable is
adequately dimensioned. The dimensioning depends on the total rated
current and must comply with EN60204-1.
•
To establish a DC link system wire the X02 connections with a suitable
cable. Voltages up to 890 V may be present.
•
The connectors are designed for a maximum current of 41 A and a
maximum conductor cross-section of 6 mm².
•
Avoid phase reversal between the devices!
The supply connection is established as described in sections 5.2.1 and 5.2.2.