5 Installation

BECKHOFF

Drive Technology

38

Version : 4.6

AX5000

5.2.3.2

Connection example - wiring in series without AX Bridge

Wire the relevant connections using individual cables.

CAUTION

Hazard to inviduals and equipment
•

Please ensure that the final supply network connection cable is

adequately dimensioned. The dimensioning depends on the total rated

current and must comply with EN60204-1.

•

To establish a DC link system wire the X02 connections with a suitable

cable. Voltages up to 890 V may be present.

•

The connectors are designed for a maximum current of 41 A and a

maximum conductor cross-section of 6 mm².

•

Avoid phase reversal between the devices!

The supply connection is established as described in sections 5.2.1 and 5.2.2.