With longer motor cables the resulting commutation currents can affect the control quality

and lead to EMC faults. Use the tables below to check whether motor chokes or mains filters

have to be used in your application. When selecting the control cabinet ensure that there is

adequate space for motor chokes, mains filters, etc.

Lay the power and signal cables in separate metal cable ducts or, if both types of cable use

the same metal cable duct, make sure there is an earthed metal dividing wall between the

cables.

Maximum cable length (including extensions) for a rated motor voltage up to 400 V

Motor choke

AX5101 - AX5112 a.AX52xx

AX5118 a. AX5125

AX5140

C2

1)

C3

C2

2)

C3

C2

C3

Without

< 25 m

< 25 m

< 25 m

< 25 m

-

< 35 m

AX2090-

MD50-0012

< 100 m

< 100 m

-

-

-

-

AX2090-

MD50-0025

-

-

< 50 m

< 50 m

-

-

1)

For compliance with EN 61800-3 only with mains filter AX2090-NF50-0014.

2)

For compliance with EN 61800-3 only with mains filter AX2090-NF50-0032.

In exceptional cases (sensitive sensors, etc.) it can be necessary to use a motor choke even

for motor cable lengths < 25 m.

Maximum cable length (including extensions) for a rated motor voltage up to 480 V

Motor choke

AX5101 - AX5112 a.AX52xx

AX5118 a. AX5125

AX5140

C2

1)

C3

C2

2)

C3

C2

C3

Without

< 20 m

< 20 m

< 20 m

< 20 m

-

< 35 m

AX2090-

MD50-0012

< 100 m

< 100 m

-

-

-

-

AX2090-

MD50-0025

-

-

< 50 m

< 50 m

-

-

1)

For compliance with EN 61800-3 only with mains filter AX2090-NF50-0014.

2)

For compliance with EN 61800-3 only with mains filter AX2090-NF50-0032.

In exceptional cases (sensitive sensors, etc.) it can be necessary to use a motor choke even

for motor cable lengths < 20 m.

Note

We recommend that feedback wires and motor wires used have the same

length.