Redundancy controller auto/manual, Redundancy controller toggle, Set physical address – Comtech EF Data CSAT-6070 User Manual

Page 72

Advertising
background image

5 to 25 Watt C-Band Transceiver

Revision 0

System Operation

MN/XSAT607025.IOM

whether or not the redundancy controller will switch on a LNA current alarm in the
redundant configuration. (The factory default is 0)

Associated Remote Command(s):

LFL=

Example(s) LFL=0

3.3.16 R

EDUNDANCY

C

ONTROLLER

A

UTO

/M

ANUAL

The Operating mode of the Comtech EF Data Redundant Switch Unit (RSU-5060) can be
set via a command to the ONLINE CSAT. The RSU-5060 initializes to the AUTO mode
when power is first applied.

• In AUTO mode the RSU-5060 monitors the state of the two CSATs and will

automatically switch the OFFLINE unit online if the ONLINE unit faults.


• In MANUAL mode, the RSU-5060 will only switch the position of the Tx and Rx

transfer switches when commanded to do so via either the RTG= command or via
Pin V on the ‘M&C Control’ connector (J5) on the RSU-5060. The user sets
AUTO mode by sending a ‘1’ in the data field and MANUAL mode with a ‘0’ in
the data field.

Associated Remote Command(s):

RAM=

Example(s) RAM=1

3.3.17 R

EDUNDANCY

C

ONTROLLER

T

OGGLE

The User can cause the RSU-5060 Redundant Switch Unit to switch the position of both
the Tx and Rx transfer switches using this command.

• If the RSU-5060 is in AUTO mode, the command will only cause a switchover if

the OFFLINE unit is currently UNFAULTED.


• If the RSU-5060 is in MANUAL mode, the command will cause a switchover

independent of the state of the OFFLINE unit.

Associated Remote Command(s):

RTG=

Example(s) RTG=

3.3.18 S

ET

P

HYSICAL

A

DDRESS

The Remote (Physical) address to which the CSAT will respond can be set to any value
between 0001 and 9999. (The factory default is 0001)

Associated Remote Command(s):

SPA=

Example(s) SPA=0001