IDLE CONSUMPTION ADJUSTMENT & TOTALIZER CALIBRATION
FloNET Interface Module
0
0
FloNET Interface Module
0
4
3
2
1
0
F
E
D
C
B
A
9
5
6
7
8
COVERED
SWITCH
BLUE
ORANGE VIOLET
GREEN
BLACK
RED
RECESSED
ARROW
16.5 GPH
293.7 GAL TOT
COMPUTER
INTERFACE
PART I: Diesel & Gasoline Generator, Diesel Electric Propulsion Engine Systems
Contact the engine dealer or refer to the engine manual-data sheet and determine the engines:
• No load fuel consumption.
1
0
F
E
D
C
B
A
9
6
7
8
5
4
3
2
0%
+2%
+4%
+6%
+8%
+10%
-2%
-4%
-6%
-8%
-10%
-12%
-14%
-16%
-18%
+12%
RED Switch
• The 10 % or 25% load, fuel consumption.
Idle Consumption Adjustment for Forward and Return, Two Sensor Generator Systems
• Start and run the engine until it is at operating temperature.
• Rotate the Red and Black switches to position “0”.
• With no load, verify that the engine is running at the correct RPM (usually 1200, 1500, or 1800).
• Rotate the Red Switch until the FloNET GPH or LPH reading matches the manufacturer’s
No-Load fuel consumption specification.
Totalizer Calibration for Forward and Return, Two Sensor Generator Systems
• Put a 10% or 25% load on the generator.
1
0
F
E
D
C
B
A
9
6
7
8
5
4
3
2
0%
+2%
+4%
+6%
+8%
+10%
-2%
-4%
-6%
-8%
-10%
-12%
-14%
-16%
-18%
-20%
BLACK Switch
• Rotate the Black Switch until the GPH reading matches the manufacturer’s 10% or 25% load fuel
consumption listing.
NOTE: Generators turning at 1200, 1500, or 1800 RPM will consume much more fuel at No Load
than propulsion engines. If you are unable to obtain the engine manufacturer’s consumption data
proceed to Part’s II and IV below. You should triple the readings in Part II, Table 1.