Flowserve MF User Manual

Page 5

Advertising
background image

MF USER INSTRUCTIONS ENGLISH 71569191 12/04

Page 5 of 50

®

HOT (and cold) PARTS

If hot or freezing components or auxiliary heating

supplies can present a danger to operators and

persons entering the immediate area action must be

taken to avoid accidental contact. If complete

protection is not possible, the machine access must

be limited to maintenance staff only, with clear visual

warnings and indicators to those entering the

immediate area.

Bearing housings must not be insulated

and drive motors and bearings may be hot.

If the temperature is greater than 68 °C (175 °F) or

below 5 °C (20 °F) in a restricted zone, or exceeds

local regulations, action as above shall be taken.

HAZARDOUS LIQUIDS

When the pump is handling hazardous liquids care

must be taken to avoid exposure to the liquid by

appropriate siting of the pump, limiting personnel

access and by operator training. If the liquid is

flammable and/or explosive, strict safety procedures

must be applied.

Gland packing must not be used when pumping

hazardous liquids.

PREVENT EXCESSIVE EXTERNAL

PIPE LOAD

Do not use pump as a support for piping. Do not

mount expansion joints, unless allowed by Flowserve

in writing, so that their force, due to internal pressure,

acts on the pump flange.

ENSURE CORRECT LUBRICATION

(See section 5,

Commissioning, startup, operation,

and shutdown

.)

START THE PUMP WITH OUTLET

VALVE PARTLY OPENED (Unless otherwise

instructed at a specific point in the User Instructions.)

This is recommended to minimize the risk of

overloading and damaging the pump motor at full or

zero flow. Pumps may be started with the valve

further open only on installations where this situation

cannot occur. The pump outlet control valve may

need to be adjusted to comply with the duty following

the run-up process. (See section 5,

Commissioning

startup, operation, and shutdown

).

NEVER RUN THE PUMP DRY

INLET VALVES TO BE FULLY OPEN

WHEN PUMP IS RUNNING

Running the pump at zero flow or below the

recommended minimum flow continuously will cause

damage to the seal.

DO NOT RUN THE PUMP AT

ABNORMALLY HIGH OR LOW FLOW RATES

Operating at a flow rate higher than normal or at a

flow rate with no backpressure on the pump may

overload the motor and cause cavitation. Low flow

rates may cause a reduction in pump/bearing life,

overheating of the pump, instability, and cavitation /

vibration.

1.6.4 Products used in potentially explosive

atmospheres

Measures are required to:

Avoid excess temperature

Prevent build up of explosive mixtures

Prevent the generation of sparks

Prevent leakages

Maintain the pump to avoid hazard

The following instructions for pumps and pump units

when installed in potentially explosive atmospheres

must be followed to help ensure explosion protection.

Both electrical and non-electrical equipment must

meet the requirements of European Directive

94/9/EC.

1.6.4.1 Scope of compliance

Use equipment only in the zone for which it is

appropriate. Always check that the driver, drive

coupling assembly, seal and pump equipment are

suitably rated and/or certified for the classification of the

specific atmosphere in which they are to be installed.

Where Flowserve has supplied only the bare shaft

pump, the Ex rating applies only to the pump. The

party responsible for assembling the pump set shall

select the coupling, driver, and any additional

equipment, with the necessary CE Certificate/

Declaration of Conformity establishing it is suitable for

the area in which it is to be installed.

The output from a variable frequency drive (VFD) can

cause additional heating affects in the motor and the

ATEX Certification for the motor must state that it is

covers the situation where electrical supply is from

the VFD. This particular requirement still applies

even if the VFD is in a safe area.

Advertising
This manual is related to the following products:

MFC, MFV, MN