7 configuration confirmation, 1 checking connections, 2 view settings – Flowserve MX HART Field Unit User Manual

Page 17

Advertising
background image

17

MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14

flowserve.com

2.7 Configuration Confirmation

Field device operation cannot be verified until the complete HART system is operational. However, routine checks can
be performed to verify many functions.

2.7.1 Checking Connections

Verify that all connections, including data wires, shield ground, digital inputs (optional), digital outputs (optional), and
analog inputs are in accordance with MX/QX wiring diagrams and MX/QX HART device diagrams in Appendix A.

2.7.2 View Settings

Refer to Installation and Operation Manual Bulletins LMENIM2306 for the MX and LMENIM3306 for the QX to access
the view settings menu. Verify the settings as follows:

1. From the VIEW SETTINGS display, scan to the VIEW HART? display
2. From VIEW HART? display, select YES and check that the HART status is ON. This confirms that HART is enabled.
3. From HART STATUS display, select YES to go to next display, which is DEVICE ID. This is the Unique Device ID of

the HART device.

4. If the MX/QX contacts are to be controlled via the network to control external equipment, from the VIEW HART?

display, select NO and obtain the VIEW STATUS AND ALARM CONTROL? display. Verify that the digital outputs,
S1a, S1b, S2a, S2b are set for “Network” controlled.

Figure 2.9 – MX/QX HART View Settings Sequence

If Hart Actuator

& Multidrop

If Hart Actuator

& not Multidrop

If fail position is

not “position”

If fail position is

“position”

VIEW

HART?

POLLING ADDRESS

(0)-OK?

PROP BAND

(5%)-OK?

DEADBAND

(2%)-OK?

ESD ACTION

(IGNORE)-OK?

MOVE TO

XXX% OPEN

FAIL POSITION

(CLOSE)-OK?

MOVE TO

XXX% OPEN

STATUS

(ON)-OK?

DEVICE ID

3295509-OK?

HART-1 FIRMWARE

REV 25-OK?

HART-1 HARDWARE

REV 25-OK?

MULTI-DROP

(DISABLED)-OK?

Advertising
This manual is related to the following products: