Flowserve MX HART Field Unit User Manual

Page 23

Advertising
background image

23

MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14

flowserve.com

Command

Request Data Bytes

Response Data Bytes

No.

Description

Byte

Format

Description

Byte

Format

Description

8

Read Dynamic

Variable Class

Read Dynamic

Variable Class

0

1

2

3

Enum

Enum

Enum

Enum

Primary Variable Class

Secondary Variable Class

Tertiary Variable Class

Quaternary Variable Class

9

Read Device

Variables with

Status

0

1

2

3

4

5

6

7

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Slot 0: Device Variable Code

Slot 1: Device Variable Code

Slot 2: Device Variable Code

Slot 3: Device Variable Code

Slot 4: Device Variable Code

Slot 5: Device Variable Code

Slot 6: Device Variable Code

Slot 7: Device Variable Code

0

1

2

3

4-7

8

9

10

11

12-15

16

17

18

19

20-23

24

25

26

27

28-31

32

33

34

35

36-39

40

41

42

43

44-47

48

49

50

51

52-55

56

57

58

59

60-63

64

65-68

Bits

Unsigned-8

Enum

Enum

Float

Bits

Unsigned-8

Enum

Enum

Float

Bits

Unsigned-8

Enum

Enum

Float

Bits

Unsigned-8

Enum

Enum

Float

Bits

Unsigned-8

Enum

Enum

Float

Bits

Unsigned-8

Enum

Enum

Float

Bits

Unsigned-8

Enum

Enum

Float

Bits

Unsigned-8

Enum

Enum

Float

Bits

Time

Extended Field Device Status: 0=OK,

1=Maintenance req’d, 2=Device Alert

Slot 0: Device Variable Code

Slot 0: Device Variable Classification

Slot 0: Units Code

Slot 0: Device Variable Value

Slot 0: Device Variable Status

Slot 1: Device Variable Code

Slot 1: Device Variable Classification

Slot 1: Units Code

Slot 1: Device Variable Value

Slot 1: Device Variable Status

Slot 2: Device Variable Code

Slot 2: Device Variable Classification

Slot 2: Units Code

Slot 2: Device Variable Value

Slot 2: Device Variable Status

Slot 3: Device Variable Code

Slot 3: Device Variable Classification

Slot 3: Units Code

Slot 3: Device Variable Value

Slot 3: Device Variable Status

Slot 4: Device Variable Code

Slot 4: Device Variable Classification

Slot 4: Units Code

Slot 4: Device Variable Value

Slot 4: Device Variable Status

Slot 5: Device Variable Code

Slot 5: Device Variable Classification

Slot 5: Units Code

Slot 5: Device Variable Value

Slot 5: Device Variable Status

Slot 6: Device Variable Code

Slot 6: Device Variable Classification

Slot 6: Units Code

Slot 6: Device Variable Value

Slot 6: Device Variable Status

Slot 7: Device Variable Code

Slot 7: Device Variable Classification

Slot 7: Units Code

Slot 7: Device Variable Value

Slot 7: Device Variable Status

Slot 7 data time stamp

11

Read Unique

Identifier

Associated

With Tag

0-5

Packed

Tag

0

1-2

3

4

5

6

7

7

8

9-11

12

13

14-15

16

17-18

19-20

21

Unsigned-8

Enum

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-5

Enum

Bits

Unsigned-24

Unsigned-8

Unsigned-8

Unsigned-16

Bits

Enum

Enum

Enum

“254”

Expanded Device Type = 0x3008

Min. number of request preambles = 5

HART Protocol Major Rev. = 7

Device Rev. Level

Software Rev. Level

(5 MSB) Hardware Rev. Level

(3 LSB) Physical Signaling Code=0

Device Flag Assignment = 0

Device ID (unique for given device type)

Min. number of response preambles=5

Max. number of device variables = 5

Configuration Change Counter

Extended Field Device Status: 0=OK,

1=Maintenance req’d, 2=Device Alert

Manufacturer Identification Code = 0x0030

Private Label Distributor Code = 0x0030

Device Profile = 1

12

Read Message

0-23

Packed

Message

13

Read Tag,

Descriptor,

Date

0-5

6-17

18-20

Packed

Packed

Date

Tag

Descriptor

Date Code

14

Read Primary

Variable

Transducer

Information

0-2

3

4-7

8-11

12-15

Unsigned-24

Enum

Float

Float

Float

Transducer Serial Number

Transducer Limits and Minimum Span Units

Code = 57 (%)

Upper Transducer Limit

Lower Transducer Limit

Minimum Span

15

Read Device

Information

0

1

2

3-6

7-10

11-14

15

16

17

Enum

Enum

Enum

Float

Float

Float

Enum

Enum

Bits

PV Alarm Selection Code = 250 (not used)

PV Transfer Function Code = 0 (Linear)

PV Upper and Lower Range Values Units

Code

PV Upper Range Value

PV Lower Range Value

PV Damping Value (seconds)

Write Protect Code = 251 (none)

Reserved = 250 (not used)

PV Analog Channel Flags = 0x01

Advertising