Flowserve MX HART Field Unit User Manual

Page 48

Advertising
background image

MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14

48


Click OK to continue with calibration of ranges.

The current Lower (LRV) and Upper (URV) ranges are shown. To change the range value, click on the item to be
changed; a new window will open, allowing the user to set both limits at the same time.

To change the lower range value, click on PV LRV item; a new window will open, allowing the user to enter the value.

Advertising
This manual is related to the following products: