MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14

46

Set the Analog Input Loop Current to the high reference value (typically 20 mA, but can be set between 12-28 mA)
and then click OK.

Enter the measured value of the loop current in mA that was applied in the previous step.

A verification of the reference values that were set will be displayed. Click OK to complete the calibration.