MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14

32

Command

Request Data Bytes

Response Data Bytes

No.

Description

Byte

Format

Description

Byte

Format

Description

105

Read Burst

Mode

Configuration

34

0

Unsigned-8

Burst Message

0

1

2

3

4

5

6

7

8

9

10

11

12-13

14-17

18-21

22

23

24

25-28

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-16

Time

Time

Enum-8

Enum-8

Enum-8

Float

Burst Mode Control Code

31 (0x1F) Command Number Extension Flag

39

Device Variable Code Slot 0

40

Device Variable Code Slot 1

Device Variable Code Slot 2

Device Variable Code Slot 3

Device Variable Code Slot 4

Device Variable Code Slot 5

Device Variable Code Slot 6

Device Variable Code Slot 7

Burst Message

Maximum Number of Burst Messages

Extended Command Number

Update Time (1/32 of a millisecond)

Maximum Update Time (1/32 of a millisecond)

Burst Trigger Mode Code

Device Variable Classification for Trigger Value

Units Code

Trigger Value

106

Flush Delayed

Responses

34

107

Write Burst

Device

Variables

34

0

1

2

3

4

5

6

7

8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Device Variable Code Slot 0

Device Variable Code Slot 1

Device Variable Code Slot 2

Device Variable Code Slot 2

Device Variable Code Slot 4

Device Variable Code Slot 5

Device Variable Code Slot 6

Device Variable Code Slot 7

Burst Message

0

1

2

3

4

5

6

7

8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Device Variable Code Slot 0

40

Device Variable Code Slot 1

Device Variable Code Slot 2

Device Variable Code Slot 2

Device Variable Code Slot 4

Device Variable Code Slot 5

Device Variable Code Slot 6

Device Variable Code Slot 7

Burst Message

108

Write Burst

Mode

Command

Number

34

0-1

2

Unsigned-16

Unsigned-8

Command Number of the response message

to be transmitted

41

Burst Message

0-1

2

Unsigned-16

Unsigned-8

Command Number of the response message to

be transmitted

Burst Message

109

Burst Mode

Control

42

0

1

Unsigned-8

Unsigned-8

Burst Mode Control Code

Burst Message

0

1

Unsigned-8

Unsigned-8

Burst Mode Control Code

Burst Message

115

Read Event

Notification

Summary

43

0

Unsigned-8

Event number = 0

44

0

1

2.7-2.4

2.3-2.0

3-6

7-10

11-14

15-18

19-44

Unsigned-8

Unsigned-8

Bits-4

Enum

Time

Time

Time

Time

Bits

Event Number

Number of events supported

MS 4 Bits of Event Status

LS 4 Bits of Event Notification Control Code

Time when first unacknowledged event was

triggered

45

Event Notification Retry Time

Maximum Update Time

Event De-bounce Interval

Event Mask

46

116

Write Event

Notification Bit

Mask

43

0

1-27

Unsigned-8

Bits

Event Number = 0

44

Event Mask

47

0

1-27

Unsigned-8

Bits

Event Number = 0

Event Mask

117

Write Event

Notification

Timing

43

0

1-4

5-8

9-12

Unsigned-8

Time

Time

Time

Event Number = 0

44

Event Notification Retry Time

Maximum Update Time

48

Event De-bounce Time

0

1-4

5-8

9-12

Unsigned-8

Time

Time

Time

Event Number = 0

Event Notification Retry Time

Maximum Update Time

Event De-bounce Time

118

Event

Notification

Control

43

0

1

Unsigned-8

Unsigned-8

Event Number = 0

44

Event Notification Control Code

0

1

Unsigned-8

Unsigned-8

Event Number = 0

Event Notification Control Code

119

Acknowledge

Event

Notification

43

0

1-4

5-6

7

8-32

Unsigned-8

Time

Unsigned-16

Bits

Bits

Event Number = 0

44

Time when first unacknowledged event was

triggered

Configuration Changed Counter

Device Status

Command 48 Data

0

1-4

5-6

7

8-32

Unsigned-8

Time

Unsigned-16

Bits

Bits

Event Number = 0

Time when first unacknowledged event was

triggered

49

Configuration Changed Counter

Device Status

Command 48 Data

512

Read Country

Code

1-2

3

Unsigned-8

Enum-8

Country Code

50

SI Units Only

513

Write Country

Code

1-2

3

Unsigned-8

Enum-8

Country Code

50

SI Units Only

1-2

3

Unsigned-8

Enum-8

Country Code

50

SI Units Only

5. The Range Values allow the Loop Current to be converted to a percent for use by the actuator (e.g. to use as the actuator setpoint).
6. Issuing this command will write the current Primary Variable value to the Upper Range Value.
7. Issuing this command will write the current Primary Variable value to the Lower Range Value.
8. The Loop Current may not reflect the process while the Self test is executing. A master must not generate spurious error messages or disconnect form the Field Device

while the Self test is in progress.

9. This is equivalent to cycling the power off and then back on to the Field Device. Communication with the network will be temporarily lost. The device will not respond

to subsequent commands until the reset is complete. In addition the Loop Current may not reflect the process while the Device Reset is executing. A master must not

generate spurious error messages or disconnect from the Field Device while the Device Reset is in progress.

10. This trim is typically performed by adjusting the Loop Current to 4.00 milliamperes and sending the measured value to the Field Device. In response the Field Device trims

its calibration of the Loop Current to match the value received from the Master. Response Code 9 “Incorrect Loop Current Mode or Value” will be returned if the device is

not in the proper mode to allow the Loop Current to be calibrated or if the current is not set to exactly the minimum value.