Worcester actuation systems – Flowserve DFP17 User Manual

Page 30

Advertising
background image

30

DataFlo Digital Electronic Positioner DFP17 Installation, Operation and Maintenance Instructions

WCAIM2037

7.3 Troubleshooting Guidelines

Use the following troubleshooting guidelines to isolate
problems/bad components.

Prior to beginning any procedure, read all of Check, Action, and
Note and Caution sections.

Flow Control

Worcester Actuation Systems

CHECK

ACTION

NOTES AND CAUTIONS

7.3.1

Check for proper AC/DC power to

Correct as necessary.

actuator and circuit board. See
Figures 4, 5, 6 or 7.

7.3.2

With power off, check for broken

Repair broken wires and

wires and/or loose connections.

tighten loose connections.

7.3.3

With power off, check to see if

Remove F1 from socket pins

Before restoring power, try to determine

fuse F1 is blown. (For DC boards,

and check for continuity

what caused F1 to blow and correct

see section 7.1.2 also.)

through fuse with an

problem. See Section 3.2 note and

ohmmeter. If F1 is bad,

section A of Section 1.1,

replace it with a new fuse.

and also section 7.1.2.

7.3.4

Check operation of basic actuator

See Section 7.1.

This check will isolate the problem to either

per Section 7.1.

the actuator or the circuit board.

7.3.5

Check for proper range of input

Use ammeter, voltmeter or

See models listed at beginning of IOM for

signal.

ohmmeter to verify input

ranges. 4-20 mA is most common.

signal range.

7.3.6

With power off, check calibration

A quick check to see if this is

When trying to move the valve manually

of feedback potentiometer per

the problem is to declutch the

with the clutch disengaged, be certain that

section D of Section 1.1.

actuator shaft and reposition

the wrench fits properly on the flats of the

the shaft to about 45° (if

actuator shaft. Improper fit can cause shaft

valve torque permits). If the

damage with consequent damage to cover

actuator now runs normally

bearing surface. Stay within the preset

in each direction (after clutch

bearing surface. Stay within the preset

reengages), recalibrate the

quadrant of operation. See section C of

feedback potentiometer.

Section 1.1.

7.3.7

Check to see that varying input

If LEDs do not turn on and

The turning on and off of the LEDs is

signal from 4-20 mA causes the

off, replace board.

indicative that the input side of the circuit

light emitting diodes (LEDs) to

board is OK.

turn on and off individually.

7.3.8

Check the operation of the

If intermittent or jittery

Increasing the deadband may help to

Positioner with a portable,

operation stops, it is

alleviate the problem.

battery operated signal source.

indicative of a noisy online
signal input. To avoid
damaging the actuator, it is
necessary to “clean up” the
signal. Also, follow the
shielding guidelines of
sections 1.2 and 1.2.3.

7.3.9

Check the motor run capacitor for

Replace as necessary.

Disconnect all leads from capacitor

a short, excessively high leakage

terminals (power off) prior to testing. Do

and low capacitance. Use a

not exceed rated voltage of capacitor. Make

capacitance meter to check.

certain that capacitor is discharged before

(AC boards only.)

reconnecting.

Advertising