Worcester actuation systems – Flowserve DFP17 User Manual

Page 31

Advertising
background image

WCAIM2037

DataFlo Digital Electronic Positioner DFP17 Installation, Operation and Maintenance Instructions

31

Flow Control

Worcester Actuation Systems

CHECK

ACTION

NOTES AND CAUTIONS

7.3.10

Check temperature of motor(s).

Allow the motor(s) to cool so

Duty cycle is specified at an ambient

One AC motor has a thermal

that the thermal switch can

temperature of 70°F, 60 Hz.

cutout switch built-in that opens

reset. Normally the thermal

at about 210°F (winding

switch will not open unless

temperature). If the thermal

the motor’s rated duty cycle is

cutout has opened, both motors

exceeded and/or the ambient

are de-energized until the thermal

temperature is very high.

switch resets (20-2375 sizes).

Correct the problem.

7.3.11

Check the operating torque of the

If operating torque of valve

If the actuator is removed from a three-piece

valve. If necessary, remove the

exceeds the specified torque

valve that requires the body bolts to also be

actuator from the valve. Measure

for the seats used and the DP

removed, the valve body bolts must be

valve torque with an accurate

across the valve, determine

retorqued to specifications before checking

torque wrench. Check torque

cause and correct. If torque

valve torque. See Valve IOM.

under actual operating conditions

falls within normal range, it

if possible.

is possible that the actuator is
undersized.

7.3.12

Check ambient temperature.

Actuator duty cycles are

Higher ambient derates duty cycle.

specified at an ambient
temperature of 70°F.

7.3.13

Check to see that mechanical

Replace defective mechanical

All 2" CPT valves with Positioner boards in

brake is operating correctly.

brake. If one was never

actuator must have mechanical brake

installed, order a kit and

installed to prevent oscillation.

install it in actuator.

7.3.14

Check to see if actuator can move

If motor(s) cannot start, go to

a high torque valve from a stop

next larger size actuator.

under load when moving in the
same direction as last command
(mechanical brake does not allow
motor(s) to unwind).

7.3.15

Check to see which direction of

Replace circuit board.

travel causes problem. If actuator
is coming off open limit switch
(traveling CW) when it slows
down or stops, then either Q1 or
U1 is bad. If actuator is coming
off closed limit switch (traveling
CCW), then either Q2 or U2 is
bad. (AC boards only.)