The status indicator LED flashes rapidly (approx. twice every second)
Cause:

Contact faults, only in 4-relay mode (e.g. there is a break in the cable between
the ripple control signal receiver and the Fronius Power Control Card, or it has
not been connected)

Remedy:

Check cable and connections

Cause:

The ripple control signal receiver is faulty, only in 3 and 4-relay mode (e.g. no
relay has picked up or more than one relay has picked up).

Remedy:

Check cable and connections
Check relay functions on the ripple control signal receiver
Set the operating mode adjusting dial to 0 "Test mode";
if the LED is still flashing, an EEPROM error has occurred

Cause:

No ripple control signal receiver is connected in 4-relay mode.

Remedy:

Select "Operation without ripple control signal receiver" mode

Cause:

Internal error

Remedy:

Contact After-Sales Service

Cause:

Invalid relay state in CEI 0-21-compliant operation
(more than one relay has picked up or an invalid relay has picked up)

Remedy:

Check relays

NOTE! If the ripple control signal receiver is faulty, 100% of the maximum possi-
ble output power of the photovoltaic system is fed into the grid.