POWER PRODUCT GROUP

Phone: 973-785-4347 Fax: 973-785-3318 Web: www.fsrinc.com E-Mail: [email protected]

FSR

SPC-20 SPECIFICATIONS

AC INPUT

120VAC, 60 Hz, 20Amps max.

AC INPUT:

Full line conditioning and RFI suppression

AC SWITCHING:

Solid state zero crossing (no relays that bounce,

arc,

and

pit)

AC OUTLETS:

Surge suppression on all outlets

AC OUTLETS:

Total

of

fi ve outlets, two (one on the front panel

and one on the rear panel) are active, the other
three are switched on/off in sequence. Total out-
put current must not exceed 16 Amps. Each
AC outlet is rated at 16 Amps but remember
that the total current out of the SPC-20 must
not exceed 16 Amps.

SURGE PROTECTION: Spike protection modes: Line to neutral, neutral to

ground,line to ground Spike protection voltage:

Max clamping voltage 340V peak, L-N, N-G, L-G

Response time: 1 nanosecond

Maximum surge current: >100,000 AMPS (8x20

usec pulse)

Maximum spike energy: >1000 joules

Noise attenuation: Differential 13 dB @ 150 kHz

ncreasing to 45 dB @ 30 Mhz

Common mode: 15 dB @ 150 kHz, increasing to

>45 dB @ 30 Mhz

SWITCHING DELAY: 1 to 50 seconds adjustable on the rear panel. This is the delay

from circuit 1 to circuit 2. All subsequent delays will be one
to three seconds, dependent on the adjustment.

Example:
When the SPC-15 power is powered up, via either the front panel power switch or via
remote triggering and you have chosen to set the delay to 20 secs:

The SPC-15 “circuit 1” turns on within 1 sec.
Then, the SPC-15 “circuit 2” turns on in 20 secs.
Then, the SPC-15 “circuit 3” turns on in 22 secs.
Then, the fi rst SPC-15X expansion module turns on in 24 secs.
Then, the second SPC-15X expansion module turns on in 26 secs. and so on for
additional SPC-15X modules.

When the SPC-15 power is powered down, via either the front panel power switch or
via remote triggering, all delays happen in reverse:

The last SPC- 15X expansion module turns off fi rst. Additional SPC-15X expan-
sion modules will continue to turn off in sequence at 2 second intervals.
Then, 2 secs later, after all the SPC-15X expansion modules have sequenced off,
the SPC-15 “circuit 3” turns off
Then, 20 seconds later, the SPC-15 “circuit 2” turns off
Then, within one sec, “circuit 1” turns off

REMOTE CONNECTOR: Includes all connections for remote control of the unit (

pluggable screw terminal connector)

REMOTE CONTROL: Momentary or maintained closure will operate

this

equipment. A lamp feedback signal (voltage) is also provid-
ed.

EXPANSION CONNECTOR: Feeds the fi rst expansion unit if used data connector 6

wide RJ 12) wire this connector straight through.

NOTE: THIS IS NOT TO BE USED AS A TELECOM INPUT. DO NOT PLUG A
TELEPHONE INTO THIS CONNECTOR

SIZE:

19” wide, 1.75”high and 8.5” deep

WEIGHT:

14 lbs