Configuration 2

The second configuration uses two supervised input
circuits and does not make use of the single relay
output. This configuration is accomplished by
interfacing to terminal block TB3-23 and TB3-24 for IN
1 and TB3-25 and TB3-26 for IN 2.

The external dry contact switch, either normally open or
normally closed respectively, should be in parallel to a
15 k-ohm resistor as shown in Figure 9.

A 5.1 k-ohm resistor should be in series to the 15
K-ohm resistor. This provides a voltage divider network
used to detect a short or open across the external
circuit’s cabling.

This configuration requires that the orange wire from
TB3-23 going to the relay output circuit be disconnected
so as not to interfere with supervised operation.

Another method of performing supervision using
multiple switches is shown in Figure 10. This method
requires only one 20 k-ohm resistor that is placed in
parallel to multiple normally open dry contact switches
at the end of line (EOL).

Figure 9. PLC or Switch Box

Normally Open and Normally Closed - Example

Figure 10. Input Line Supervision Multiple Switch - Example