10 heartbeat, 11 irt mode – ifm electronic RN7003 User Manual

Page 21

Advertising
background image

UK

CANopen encoder

21

To save the PDO mapping in the EEPROM transmit:

ID

Data

Note

60F 23 10 10 02 73 61 76 65 Save all communication parameters by trans-

mitting the ASCII code for "SAVE" to object

0x1010, subindex 2

Heartbeat

6.10
The RM and RN type encoders can act as heartbeat producer� The time between

two heartbeats is configured in the object "producer heartbeat time" (0x1017) and

is in the millisecond range (1���65535)� If the "producer heartbeat time" (0x1017) is

zero (0), heartbeat is deactivated�
The object "producer heartbeat time" (0x1017) is stored in the non-volatile

EEPROM and reloaded at start-up�

IRT mode

6.11
In order to enhance the real-time characteristics the encoder can operate in the

IRT (Isochronous Real Time) mode� In the normal operating mode the position

value is sampled cyclically every 0�5 ms� If "read position at SYNC" is disabled, the

PDO2 (transmit data at SYNC) uses the last sampled position of the encoder� This

adds a non real-time characteristics to the output position value� In the IRT mode

"read position at SYNC" is set� The position value is only sampled if the SYNC

message is received�
If the bit "read position at SYNC" is set in the operating parameter object (0x6000),

the following changes are made:

The speed object (0x6030) and the acceleration object (0x6040) are disabled

because the cyclic position sampling is mandatory for calculating these values�
PDO1 (transmit data cyclically) is disabled, object 0x1800, subindex 1, bit 31 is

set and stored in the EEPROM�
The object "transmit PDO1" (0x1800) is only read if the bit "read position at

SYNC" is set�
PDO2 (transmit data at SYNC) is only set to transmit position data and the new

PDO2 mapping is stored in the EEPROM�
The object "PDO2 tx mapping" (0x1A01) is only read if the bit "read position at

SYNC" is set�

If the speed and acceleration values are needed during operation in the IRT

mode, it is recommended to calculate these values in the master applica-

tion and to use the master clock (SYNC message) as a reference�

Bit

Parameter

0

code sequence