CANopen encoder

9

The (+) terminal is used for the connection to the +U

B

line (9���36 V DC)� The (-)

terminal is used for the connection to the 0 V line�

BUS lines

4.6

� � � �

� � � �

� � � �

bus output

1:

bus input

2:

Function

Terminal

CAN shield

cable gland

CAN GND

G

CAN_H

H

CAN_L

L

The cable glands of the encoder must be equipped with a twisted pair cable

according to EN50170� The guidelines recommend a wire cross-section > 0�34

mm

2�

� The permissible outer cable diameter is ø 6 ��� to ø 8 mm� Six screw

terminals with the required bus line terminals marked H, L and G are in the

terminal chamber�

Connect the (H) terminal to the CAN_H cable�

Connect the (L) terminal to the CAN_L cable�

Connect the (G) terminal to the CAN_G cable�

The G, H and L terminals are internally connected to each other so that

the bus cables can be connected to any pair�