Connecting multiple cables – Infloor Electric Cable Series 386 User Manual

Page 25

Advertising
background image

25 of 36

Copyright ©2014

G

G

Load 1

Line 1

Line 2

Black

Black

White

White

Load 2

Connecting Multiple Cables

Multiple cables can be connected to
a single Infloor thermostat or Infloor
relay. Refer to Table 2 and Table 5 for
details on calculating the maximum
number of cables per control or relay.

Power Lead

From Infloor

Electric

Cable 1

Infloor Electric

Cable Connections

(Junction Box

Near Cables)

Infloor Thermostat

or Relay

Power Supply (120

VAC or 240 VAC)

Power Lead

From Infloor

Electric

Cable 2

Standard NM

Cable (12 or

14 AWG)

To prevent the risk of personal injury and/or death, do not perform any electrical work
unless qualified to do so. Work should be done with great care and with power turned off
to the circuit being worked on. Follow all local building and electrical codes.

The Infloor thermostat is not fully illustrated in these diagrams in order to simplify them.
These diagrams are given only as examples of how to properly connect multiple cables.
Care must be taken not to overfill a box. Be sure to use wire nuts that are the correct size
for the connections being made. Follow all codes for wiring.
All electrical work must be done by a qualified licensed electrician in accordance with local
building and electrical codes, and the National Electrical Code (NEC), especially Article
424 of the NEC, ANSI/NFPA70 and Section 62 of CEC Part 1.

Infloor Thermostat / Relay Connections