20 Installation

7. Mount distribution head assembly to the topmost evaporative cassettes:

• This step must only be carried out on evaporative cassettes with glass fibre media: mount the

appropriate distribution cassettes onto the corresponding evaporative cassettes. Then, fix the

distribution cassettes to the evaporative cassettes using the plastic rivets supplied.

• Mount the appropriate distribution heads onto the corresponding evaporative cassettes or dis-

tribution cassettes respectively. Then, fix the distribution heads to the evaporative cassettes or

distribution cassettes respectively using the plastic rivets supplied.

Evaporative cassettes with

glass fibre

Evaporative cassettes with

polyester

Fig. 10: Mount distribution head assembly to the topmost evaporative cassettes