25

Installation

4.3.2 Mounting the Hydraulic manifold (external installation)

Clearances to be observed

Fig. 15: Clearances to be observed when mounting the Hydraulic manifold externally

25 mm

(0.98

")

43 mm

(1.69

")

95 mm

(3.74")

5 mm

(0.2

")

8.5 mm

(0.33")

450 mm

(17.72")

311 mm

(12.24

")

182 mm

(7.17")

157 mm

(6.18

")

1

3

2

5

4

14.5 mm

(0.57

")

STAGE VALVES **

(normally open)

DRAIN VALVE **

(normally open)

INLET VALVE **

(normally closed)

PURGE VALVE **

(normally closed)

MINIMUM 25 mm (0.98") CLEARANCE TYP.

** coil voltage: 24 Vdc

MINIMUM CLEARANCE OF

151 mm (5.94") REQUIRED

AHU WALL

DETAIL A

DETAIL A

WHEN PLANNING THE INSTALLATION OF A

ME DIRECT FEED SYSTEM (WITH EXTERNAL

HYDRAULICS) THE CLEARANCE REQUIRED

(OUTSIDE THE AHU) FOR THE FOLLOWING

SHOULD BE CONSIDERED:

• DISTRIBUTION HOSES

• FEED THROUGH PLATES

• INLET ASSEMBLY

• DRAIN PLUMBING

• DRAIN TRAP